Yearly Checklist
1
.
Test (leak test) safety shut-off valves for tightness of closure.
2
.
Test pressure switch settings by checking switch movements against pressure
setting and comparing with actual impulse pressure.
3
.
Visually check ignition cable and connectors.
4
.
Make sure that the following components are not damaged or distorted:
• the burner nozzle
• the spark plugs
• the flame sensors
• the flame tube or combustion block of the burner