Table 5: Controls and LED Indicators
Indicator
Alarm Silence Button
Cold Start Button
AC/DC Mode LED
Battery Missing LED 1&2
DC Output LED
Color
Black
Black
Green/
Orange
Red 
Green
Condition
Press and hold the button for 1 second to 
silence the audible alarm for 24 hours.
Press and hold the button for 10 seconds to 
shut down the output voltage. The UPS will 
restart after 15 seconds.
Note: The second function can be utilized to 
reset an output if it has been shut-down due to 
an over-current or short condition, and the fault 
has been removed.
The cold start allows a start-up of the system 
after a power outage and the batteries have 
been replaced.
Note: Before using the Cold Start feature, 
make sure the batteries are fully charged.
When the LED is green, the UPS is running on 
AC power.
When the LED is orange, the UPS is running 
on battery power.
The appropriate battery string is not connected 
or needs replacing. 
When lit, the UPS is outputting DC power 
whether in utility or battery power mode.
5.2  Controls and Operational LEDs
Four status LEDs are displayed on the front panel of the UPS.  The operation of the UPS can be 
assessed using these LEDs.