INSTALLATION AND OPERATION MANUAL
MF3500G, MF3500S, MF3500B Models
Page 4
800-345-6007
CumberlandStoveWorks.com
VENTING
The following installation guidelines must be followed to 
ensure conformity with both the safety listing of this stove 
and to local building codes.
note:  where passage through a wall, or partition of 
combustible construction is desired, the installation 
shall conform to Can/CSa -8365. 
TYPE OF VENT
Pellet venting pipe (also known as L vent) is constructed 
of two layers with air space between the layers. This air 
space acts as an insulator and reduces outside surface 
temperature of pipe to allow a clearance to combustibles 
of only 3”. 
A UL listed 3” or 4” type L pellet vent exhaust system must 
be used for installation and attached to the pipe connector 
provided on the back of the stove. Use a 3” to 4” adapter 
for 4” pipe. A cap must be used at the termination of type 
L vent chimneys. For elevations above 2,500 feet above 
sea level, a 4” L is required. 
PELLET VENT INSTALLATION
Termination  must  exhaust  above  air  inlet  elevation. 
Installation 
MUST include three vertical feet of pellet vent 
pipe. 
This will create some natural draft to prevent the possibility 
of smoke or odor during appliance shutdown and to keep 
exhaust from causing a nuisance or hazard from exposing 
people or shrubs to high temperatures. 
The  installation  must  include  a  clean  out  tee  to  enable 
collection of fly ash and to permit periodic cleaning of the 
exhaust system. 90º elbows accumulate fly ash and soot 
thereby  reducing  exhaust  flow  and  performance  of  the 
stove. Each elbow or tee reduces draft potential by 30% to 
50%. Use no more than 180º of elbows (two 90º elbows, 
or two 45º and one 90º elbow, etc.) to maintain adequate 
draft. 
Total length of horizontal vent must not exceed 10 feet. The 
maximum recommended vertical venting height is 12 feet 
for 3” type L vent. All joints for connector pipe are required 
to be fastened with at least three screws and all pellet vent 
connections must be sealed according to manufacturer’s 
recommendations. 
The area where the vent pipe goes through to the exterior 
of the home must be sealed with silicone or other means 
to maintain the vapor barrier between the exterior and the 
interior of the home. 
WARNING
DO  NOT  CONNECT THIS  UNIT TO  A  CHIMNEY  FLUE
SERVING ANOTHER APPLIANCE.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST
VENTING SYSTEM OF THIS UNIT.
DO  NOT  CONNECT  DIRECTLY  TO  A  MASONRY
CHIMNEY.
DO NOT TERMINATE VENT IN ANY ENCLOSED OR SEMI-
ENCLOSED  AREA,  SUCH  AS;  CARPORTS,  GARAGE,
ATTIC, CRAWL SPACE, UNDER A SUN DECk OR PORCH,
NARROW WALkWAY  OR  CLOSED  AREA,  OR  ANY
LOCATION THAT CAN BUILD UP A CONCENTRATION
OF  FUMES  SUCH  AS  A  STAIRWELL,  COVERED
BREEZEWAY ETC.
CAUTION
VENT SURFACES CAN GET HOT ENOUGH TO CAUSE
BURNS IF TOUCHED BY CHILDREN. NONCOMBUSTIBLE
SHIELDING OR GUARDS MAY BE REqUIRED.
PELLET VENT  MUST  MAINTAIN  A  MINIMUM  3  INCH
CLEARANCE TO ANY COMBUSTIBLE.
INSTALL VENT  AT  CLEARANCES  SPECIFIED  BY THE
VENT MANUFACTURER.
ALL VENTING, WHETHER VERTICAL OR HORIZONTAL,
JOINTS  SHOULD  BE  MADE  GAS  TIGHT  WITH
RECOMMENDED SEALANTS.