APC AR2400 Manual De Usuario

Descargar
Página de 34
9
NetShelter SV User Manual
Secure the Cabinet
To secure the cabinet to the floor, use fastener locations on the outside or inside of the cabinet and the 
bolt-down brackets (provided).
Ground the Cabinet
Each cabinet should be bonded directly to a common ground using the designated grounding location 
(two M6 threaded inserts) at the bottom rear of the cabinet.
•  Use a Common Bonding Network Jumper kit (not provided). For example, Listed [KDER] 
Panduit
®
 RGCBNJ660PY or equivalent.
•  Use paint-piercing washers between ground terminal and cabinet frame or remove paint on frame 
under ground terminals per NEC NFPA 70 Article 250.12
•  Torque screws to (60 in-lb, 6.8 N-m).
Bonding Location on the Cabinet 
 NOTICE
Bolt-down brackets secure the cabinet to the pallet during shipment. Remove them from 
the cabinet and pallet and save them to secure the cabinet to the floor during installation.
WARNING
TIP HAZARD
Secure the cabinet to the floor before installing equipment.
Failure to follow these instructions can result in serious injury or equipment 
damage.
ns2011a
ns2012a