Single Zone Gas Monitor 
22 
P/N: 3015-4256 Rev 13 
SQUELCH
 – Sets a value of between 0.0 and 99.9 ppm that prevents 
the display of measurements below that value. Factory default is 0 ppm. 
For example, if the squelch setting is set to 50 ppm, then the monitor will 
not display measurements that are below that value. Use the Keypad to 
enter the desired value, and then press ENTER  to save that value and 
return to the previous screen. 
 
ZONETEMP
  –  Used to enter the temperature of the area being 
monitored in °C, thus giving a  more accurate ppm reading. The factory 
default is 25°C. Use the Keypad to enter the desired temperature, and 
then press ENTER to save that value and return to the previous screen. 
 
CAL
 – Used to change the monitor’s calibration factor. This function is 
to be used ONLY with instructions from a Bacharach Service Center. 
Factory default is 1.000. 
 
P-CHK
  –  This  Pressure Check function displays the current manifold 
pressure and the stored ambient pressure in psia, along with the 
difference between these two pressures and the current fault code. 
 
 
3.4.  Gas Alarms 
3.4.1.  Overview 
If the selected  gas  ppm  level  in the area being monitored exceeds  its  preset  Leak,  Spill,  or Evacuate 
Alarm level  (page  22),  the  SZ  unit  will detect this  alarm condition and turn ON  the  front panel  ALARM 
light. Additionally, an external alarm device may activate and the monitor’s internal audible alarm may 
sound if those features have been enabled (pages 14 and 22). 
3.4.2.  Clearing / Silencing a Gas Alarm 
Once the gas-alarm circuit has been triggered all alarm indicators remain turned ON, even after the 
detected gas level returns to normal. Press the SILENCE button to clear all gas-alarm indicators after the 
cause of the alarm has been cleared and the detected gas level has dropped below all alarm levels.  
Pressing the SILENCE  button while a gas-alarm  condition  still  exists causes  the internal audible alarm 
and all external alarm devices that are connected to the relays to turn OFF for a period of time as set by 
the SILENCE function (page 22).  This will allow ventilation equipment tied to the SPILL and EVAC relays 
to continue operating. The front panel ALARM light remains ON, however, as an indication that an alarm 
condition still exists, but will automatically turn OFF once the gas level returns to normal. The alarm circuit 
will reactivate at the end of the silence period if the detected gas level is still above an alarm level. 
3.4.3.  Viewing the Gas Alarm Log 
From the Data Display screen, use the Keypad buttons to place the arrow (>) on the display next to the 
ALARMS function. Then press ENTER to display the alarm log. 
The alarm log shows  the type of alarm (LEAK, SPILL, or EVAC), plus the date and time it occurred.  If 
CLEAR is displayed, this indicates that an alarm was acknowledged at the date and time shown. 
Immediately after selecting the ALARM function, the most recent alarm event is displayed. In the example 
below, record  #03  shows that a Spill Alarm occurred on 11/10/10  at 15:06. Note that if more than 
30 alarm events have occurred, then the newest event overwrites the oldest.  The Alarm Log can be 
cleared as described on page 25. 
 
#03     SPILL @ 
11/10/10  15:06 
14.72 * AMB14.81 
 0.0 
  
 
 R134A CALFACTOR 
     1.000 
TEMP AT ZONE = 
       25 degC 
SQUELCH BELOW 
     50.0ppm