Westinghouse WGC055NG100 Instruccion De Instalación

Descargar
Página de 59
11 
 
 
                                                                                 WHL-019 REV. 12.17.14 
1. DIRECT VENT INSTALLATION OF EXHAUST VENT AND INTAKE PIPE 
If installing a direct vent option, combustion air must be drawn from the outdoors directly into the water heater intake, and exhaust must 
terminate outside. There are three basic direct vent options detailed in this manual: 1. Side Wall Venting, 2. Roof Venting, and 3. 
Unbalanced Venting. 
 
Be sure to locate the heater such that the exhaust vent and intake piping can be routed through the building and properly terminated. 
Different vent terminals can be used to simplify and eliminate multiple penetrations in the building structure (see Optional Equipment in 
Venting Section). The exhaust vent and intake piping lengths, routing and termination methods must all comply with the methods and 
limits given in the Venting section, Part 5 of this manual. 
 
When installing a combustion air intake from outdoors, care must be taken to utilize uncontaminated combustion air. To prevent 
combustion air contamination, see Table 1
 
2. INDOOR COMBUSTION AIR INSTALLATION IN CONFINED OR UNCONFINED SPACE 
This heater requires fresh, uncontaminated air for safe operation and must be installed in a mechanical room where there is adequate 
combustion and ventilating air. NOTE: To prevent combustion air contamination, see Table 1 
 
Combustion air from the indoor space can be used if the space has adequate area or when air is provided through a duct or louver to 
supply sufficient combustion air based on the water heater input. Never obstruct the supply of combustion air to the water heater. 
If the water heater is installed in areas where indoor air is contaminated (see Table 1) it is imperative that the water heater be installed 
as direct vent so that all combustion air is taken directly from the outdoors into the water heater intake connection. 
 
Unconfined space is space with volume greater than 50 cubic feet per 1,000 Btu/hour (4.8 cubic meters per kW) of the total input 
rating of all fuel-burning appliances installed in that space. Rooms connected directly to this space, through openings not furnished with 
doors, are considered part of the space. Se
, p. 38 for details. 
 
Confined space is space with volume less than 50 cubic feet per 1,000 Btu/hour (4.8 cubic meters per kW) of the total input rating of 
all fuel-burning appliances installed in that space. Rooms connected directly to this space, through openings not furnished with doors, 
are considered part of the space. 
 
When drawing combustion air from inside a conventionally constructed building to a confined space, such space should be provided 
with two permanent openings
: one located 6” (15 cm) below the space ceiling, the other 6” (15cm) above the space floor. Each opening 
should have a free area of one square inch per 1,000 Btu/hr (22cm
2
/kW) of the total input of all appliances in the space, but not less 
than 100 square inches (645cm
2
). 
 
If the confined space is within a building of tight construction, air for combustion must be obtained from the outdoors as outlined in the 
Venting section, Part 5 of this manual. 
 
 
When drawing combustion air from the outside into the mechanical room, care must be taken to provide adequate freeze protection.  
 
 
Do not attempt to vent this water heater by any means other than those described in this manual. Doing so will void the warranty, and 
may result in severe personal injury or death. 
 
 
Failure to provide an adequate supply of fresh combustion air can cause poisonous flue gases to enter living space, resulting in severe 
personal injury or death. To prevent combustion air contamination, see Table 1. 
F. PREVENT COMBUSTION AIR CONTAMINATION 
Install intake piping for the heater as described in the Venting Section. Do not terminate exhaust in locations that can allow 
contamination of intake air. 
 
 
Ensure that the intake air will not contain any of the contaminants below. Contaminated air will damage the heater, resulting in possible 
substantial property damage, severe personal injury, or death. For example, do not pipe intake near a swimming pool. Also, avoid areas 
subject to exhaust fumes from laundry facilities. These areas always contain contaminants.