Home Automation HAI (Home Automation Inc.) Home Security System 20A00-1 Manual De Usuario

Descargar
Página de 68
 
Page 45 
 
 
 
CALL BACK PHONE NUMBER 
 
In response to a request for remote PC ACCESS using the PC ACCESS code, the system will hang up and dial this number back 
immediately.  To program the CALLBACK PHONE NUMBER, enter the number then press  ' # '.  To remove the CALLBACK 
PHONE NUMBER, press the OFF key to enter a single "-", then press ' # '. 
 
 
 
 
CALL BACK PHONE NUMBER: 
 
 
 
-                      
 
 
OUTSIDE SIREN DELAY 
 
If an output is configured as an "Exterior Sounder", when the alarm is "tripped", the interior sounder is turned on first.  After the 
OUTSIDE SIREN DELAY, the outside sounder is turned on.   
 
This feature helps reduce annoying false alarms by signaling inside the premises first.  The outside siren delay is set to 15 seconds 
at the factory.  You may change it to any value from 0 to 60 seconds.  If you want the outside sounder to turn on immediately 
when the alarm is activated, set the delay to 0. We recommend a minimum time of 15 seconds. 
 
 
 
 
DIAL OUT DELAY:       15 
 
 
 
0-60 SECONDS           
↕ 
 
DIAL OUT DELAY 
 
The DIAL OUT DELAY is the number of seconds that the Omni II waits before making an emergency dial out, AFTER the alarm 
is "tripped" (activated by burglar or fire).  This delay is set at the factory to 15 seconds.  We recommend a minimum time of 15 
seconds to preclude an accidental activation of the alarm from calling in a false alarm. 
 
 
 
 
DIAL OUT DELAY:       15 
 
 
 
0-60 SECONDS           
 
 
ALARM RESET TIME 
 
The Alarm Reset Time is the time it takes before the alarm system resets itself after the alarm is tripped. 
 
 
 
 
ALARM RESET TIME:      4 
 
 
 
1-30 MINUTES           
 
 
To change the alarm reset time, enter a new time between 1-30 minutes, then press the  ' # ' key.  The default setting is 4 minutes. 
 
ARMING CONFIRMATION 
 
The Arming Confirmation is a quick pulse (squawk) given by the outside siren when the alarm system is armed into a security 
mode and the EXIT DELAY is expired. 
 
 
 
 
ARMING CONFIRMATION:   0 
 
 
 
0=NO  1=YES            
 
 
To enable the arming confirmation feature, press the 1 (YES) key, then press the ' # ' key.  The default setting is 0 (NO) disabled. 
 
FIRE ALARM VERIFICATION
 
 
This unit is equipped with a FIRE ALARM VERIFICATION feature.  When a zone configured as a FIRE (Type 32) or a GAS 
(Type 34) is activated, the system will cycle SWITCH 12V and Switched Power Outputs off for 10 seconds.  The SWITCH 12V 
power output will then be restored, and 5 seconds later, the zones will be monitored again.  If the zone is activated again within a 
2-minute window, the fire alarm will be activated.  If not, no fire alarm will be indicated. 
 
 
 
 
VERIFY FIRE ALARMS:    1 
 
 
 
0=NO 1=YES             
↕