Alarm and fault messages 
4.2 Alarm and fault messages 
40 
(Alarm) Symmetry fault 
Condition 
The S7 routine for monitoring symmetry has detected an 
imbalance 
Alarm in the PV field 
o
  Automatic fuse or fusible link in the junction 
box has tripped 
o
  Fuse at the DC input has tripped 
o
  PV module is defective 
o
  Defect in the PV field cabling 
Causes 
Alarm activated during measured-value sensing  
o
  Isolation amplifier defective 
o
 Wire 
break 
Replace the fuses (plus and minus at the same time) 
Close the automatic fuse 
Replace the PV module 
 
Measures 
Replace the PV cabling 
 
 
 
Alarm without fault 
The system uses alarms which do not have individual messages (codes). This can be identified 
according to certain alarm conditions. 
 
Inverter does not start, PPsolar signals "Manual Bypass ON"  
Cause: Power pack defective 
 
Inverter does not start; PPsolar is not displaying a DC voltage even though a DC voltage is present 
(manual measurement) 
Cause: Power pack defective 
 
Inverter does not start, PPsolar is not displaying a DC voltage 
Cause: The DC inverter PSU or the Masterdrives DC link fuse is defective. 
No DC voltage is present (the junction boxes are switched off, it is dark outside). 
 
 
Inverter is shut down completely 
Cause: No AC voltage present (infeed, external infeed)