Point Database 
Siemens Building Technologies, Inc. 
 
19 
Address Descriptor 
Description 
56 
ODP STPT SW 
Indicates if the lower left button on the ODP has been pressed. This is a toggle 
action digital input; when pressed, the controller changes between HI and LOW 
flow setpoints. 
57 
RIGHT SW 
Indicates if the right auxiliary button on the ODP has been pressed. This is a 
toggle action digital input; when pressed, the point is ON. If pressed again, the 
point is OFF. 
63 
FLOW P GAIN 
The proportional gain value for the fume hood flow control loop. 
64 
FLOW I GAIN 
The integral gain value for the fume hood flow control loop. 
66 
FLOW D GAIN 
The derivative gain value for the fume hood flow control loop. 
67 
FLOW BIAS 
The bias, in percent, of the fume hood flow control loop. 
68 
CTRL LOOPOUT 
Control output of the flow loop. Range: -100% to 100%. 
87 
FLOW HI STPT 
The hi flow setpoint used in FLOW STPT. 
89 
HORN 
When this point is set to DISABLE, the audible alarm will not sound.  All other 
alarm functionality is still operational. 
91 
BLANK DSPLY 
When set to YES, the exhaust flow is not displayed at the ODP. 
92 
DO2 INVERTER 
Setting to NCLOSE allows the controller to operate industry standard floating 
control actuators.  Setting this point may stop the failsafe operation from 
functioning. 
93 
ENG UNITS 
Toggles the display of the ODP from CFM to LPS. Toggling this point does not 
change the displayed value at the portable operators terminal. 
94 
LAMP TEST 
Turns on all lights, prompts, and the audible alarm at the ODP. 
96 
ALARM TIME 
Time delay for the red and yellow alarm LEDs used to eliminate sudden changes 
and false alarms. The exhaust flow  must rise above any of the set limits (for 
example, HI ALM LMT) for the amount of time specified at this point before the 
ODP indicates an alarm condition. 
97 
DUCT AREA 
Area of the duct, in square feet (SQM), where the air velocity sensor is located. 
98 
LOOP TIME 
The time, in tenths of a second, between control loop calculations. 
99 
ERROR STATUS 
The status code that indicates any errors detected during controller power-up.