GENERAL CHARACTERISTICS AND OPERATION
1.12 
Modular Low Impedance Bus Bar Protection M-LIB3
The M-LIB system is constituted of a number of modular units, which can be combined to suit to any
busbar configuration and allow for easy extension.
1.13 
Main features
q  
Low impedance and low burden on main CTS.
q  
High stability with zone biased differential elements and CT saturation detectors.
q  
High speed of operation.
q  
High reliability: duplicated measuring circuits, CTs’ secondary circuits supervision, wide and
consistent setting ranges
q  
Self-contained input CTs for main zone and for check zone feature without duplication of main CTs.
q  
Self-contained isolator repeat relays switching at secondary of the zone input CTs.
q  
Self-contained discrepancy alarm relays
q  
Multivoltage power supply.
q  
Comprehensive self-diagnostic.
q  
User friendly MMI.
q  
Real time and recorded measurements.
q  
Event records and oscillography
q  
RS 485 serial port with ModBus protocol.
1.14 
Component Modules
The system includes three basic modules:
1.14.1  M-BF3 = Income/Feeder Breaker input module (SCE1577)
Including :
q  
sets of three CTs.  1 set for the Main Zone and 1 for the Check Zone.
q  
CT saturation detectors.
q  
bistable isolator repeat relays for switching the secondary circuits of the input CTs  and the zone
trip input signal.
q  
Time delayed isolator discrepancy alarm feature
q  
Power supply unit