APC Condenser 2 EC Fan ACCD75208 Manual De Usuario

Los códigos de productos
ACCD75208
Descargar
Página de 50
InRow RP Technical Data Manual
18
Chilled Water Performance Specifications 7.2°C (45°F) EWT
Temperature dry bulb 
(DB), wet bulb (WB)
°C (°F)
CW Delta T
°C (°F)
Total Net 
Capacity
kW (BTU/hr)
Sensible Net 
Capacity
kW (BTU/hr)
Sensible Heat 
Ratio
SHR
 CW Flow Rate
l/s (GPM)
Total CW 
Pressure Drop
kPa (ft H2O)*
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
5.5 (10)
40.8 (139,000)
39.6 (135,000)
0.97
1.8 (28.8)
81 (27.03)
6.6 (12)
37.9 (130,000)
36.8 (126,000)
0.97
1.4 (22.5)
50 (16.6)
7.7 (14)
35.1 (120,000)
34.1 (116,000)
0.97
1.1 (18.0)
32 (10.9)
8.8 (16)
32.5 (111,000)
31.5 (108,000)
0.97
0.9 (14.6)
22 (7.4)
10 (18)
29.8 (102,000)
28.9 (99,000)
0.97
0.8 (12.0)
15 (5.1)
11.1 (20)
27.3 (93,000)
26.5 (90,000)
0.97
0.6 (10.0)
11 (3.7)
29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)
6.6 (12)
45.0 (154,000)
43.7 (149,000)
0.97
1.7 (26.4)
68 (22.6)
7.7 (14)
42.0 (144,000)
40.8 (139,000)
0.97
1.3 (21.2)
44 (14.8)
8.8 (16)
39.1 (134,000)
38.0 (130,000)
0.97
1.1 (17.4)
30 (10.2)
10 (18)
36.3 (124,000)
35.2 (120,000)
0.97
0.9 (14.4)
21 (7.2)
11.1 (20)
33.3 (114,000)
32.6 (111,000)
0.98
0.8 (11.9)
15 (5.1)
32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)
6.6 (12)
52.3 (179,000)
51.2 (175,000)
0.98
1.9 (30.4)
89 (29.8)
7.7 (14)
49.2 (168,000)
48.2 (165,000)
0.98
1.5 (24.5)
59 (19.9)
8.8 (16)
46.1 (157,000)
45.2 (154,000)
0.98
1.3 (20.2)
41 (13.6)
10 (18)
42.7 (146,000)
42.3 (144,000)
0.99
1.1 (16.7)
28 (9.5)
11.1 (20)
39.8 (136,000)
39.4 (135,000)
0.99
0.9 (14.1)
20 (6.9)
35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)
7.7 (14)
57.2 (195,000)
56.0 (191,000)
0.98
1.8 (28.3)
78 (26.1)
8.8 (16)
53.4 (182,000)
52.9 (181,000)
0.99
1.5 (23.2)
53 (17.8)
10 (18)
50.3 (172,000)
49.8 (170,000)
0.99
1.2 (19.5)
38 (12.7)
11.1 (20)
47.2 (161,000)
46.7 (160,000)
0.99
1.0 (16.5)
28 (9.2)
37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)
8.8 (16)
61.6 (210,000)
61.0 (208,000)
0.99
1.7 (26.6)
69 (23.1)
10 (18)
58.3 (199,000)
57.7 (197,000)
0.99
1.4 (22.4)
50 (16.6)
11.1 (20)
55.1 (188,000)
54.5 (186,000)
0.99
1.2 (19.1)
36 (12.2)
40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)
8.8 (16)
69.6 (238,000)
69.6 (238,000)
1.00
1.9 (29.9)
86 (28.9)
10 (18)
66.1 (226,000)
66.1 (226,000)
1.00
1.6 (25.3)
63 (21.02)
11.1 (20)
62.7 (214,000)
62.7 (214,000)
1.00
1.4 (21.7)
46 (15.5)
Note: All values are accurate to +/- 5% and based on full speed with standard filters.
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).
Note: Any CW flow rate of 0.19 l/s - 0.32 l/s (3.0 GPM - 5.0 GPM) may cause an increased error in flow rate and power calculation. A 
fluid flow fault may result. Any flow rate under 0.19 l/s (3.0 GPM) may also display as 0 in the flow rate and power calculation.
Note: For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak 
conditions.
* To convert feet of water to PSIG, use the following formula: ft H2O ÷ 2.307 = PSIG.