Friedrich SH20N50 Hoja De Datos

Descargar
Página de 2
Front
SIDE VIEW
(A)
Junction 
Box
Max.
Wall
Depth
Sleeve Dimensions Drawing
Hazardgard_Submital_2015
Specifications
T4 temperature classification means unit surface temperatures will not 
rise above 135° C/275° F.  Operates at low ambient conditions without 
freezing at outdoor ambient temperatures as low as 7° C/45° F.
Tolerates higher outdoor temperatures up to 55° C /130° F.
Equipment is certified in accordance with ISA 12.12.01 and NFPA 70-10 
(National Electric Code)
ARTICLE 501 
ARTICLE 505
Class I, Div. 2, Group A and Group B 
Class I, Zone 2, Group IIC
Class I, Div. 2, Group B 
Class I, Zone 2, Group IIB  
 
plus hydrogen, or “+H2”
Class I, Div. 2, Group C 
Class I, Zone 2, Group IIB 
Class I, Div. 2, Group D 
Class I, Zone 2, Group IIA
Due to continuing engineering research and technology, specifications are subject to change without notice. Manufactured under U.S. Design 
Patent DES 368, 306 decorative front; Utility Patent 5, 622, 058. MAXIMUM outdoor ambient operating temperature is 130°F. (55°C) MAXIMUM 
TEMPERATURE RATING FOR CLASS I, DIVISION 2, GROUPS A,B,C,D.
For global applications, Hazardgard cooling capacities are tested in a certified laboratory at moderate (T1*) and hot (T3*) climate conditions in 
accordance with SASO (Saudi Arabian Standards Organization) Standard 2681. SASO Standard 2681 is adopted from ISO Standard 5151 for testing 
and rating for performance of non-ducted air conditioners and heat pumps.
* Capacity and efficiency values at each climate conditions are available upon request. 
 
 
Installation Information
Model
Cooling Capacity 
Electrical Characteristics
Circuit Rating 
Breaker or 
T - D Fuse
Energy 
Efficiency 
Ratio
Moisture
Removal 
Air Circulation
Refrigerant
Cooling
Cooling
Btu/Hr.
Volts Rated
Amps
Watts
Volts - Amps
EER 
Pints/ HR
 CFM
6 0   H E R T Z 
SH15M30A
14500/14000
230/208
6.9/7.5
1495/1443
250V-15
9.7/9.7
4.0
375
R-410A
SH20M30B
19000/19000
230/208
8.5/9.4
1965/1970
250V-15 (230V)
9.7/9.6
5.5
375
R-410A
250V-20 (208V)
SH24N20
24000/23700
230/208
12.6/13.5
2727/2788
250V-30
8.8/8.5
8.0/7.5
385
R-401A
5 0   H E R T Z
SH20N50
19500/19100
240/220
9.8/10.3
2167/2156
250V-15
9.0/9.0
5.6/5.5
425
R-410A
SH24N20
21000/20500
240/220
15.0/13.2
2600/2412
250V-30
8.1/8.5
7.0/7.0
360
R-410A
Model
Dimensions 
INCHES
Window
 
Width 
INCHES
In-Wall Installation
Finished Hole INCHES
Weight
 
Lbs.
Height
Width
Depth with 
Front 
Depth J Box  
to Louvers
Minimum
Extension 
Into Room
Minimum 
Extension 
Outside
Min.
Max.
Height
Width Max. Depth Net Shipping
SH15M30BA
15 
15
/
16”
25 
15
/
16”
27 
3
/
8”
6
1
/
16”
16 
15
/
16”
27 
7
/
8”
42
16 
3
/
16”
26 
3
/
16”
6
140
167
SH20M30B
17 
15
/
16”
25 
15
/
16”
27 
3
/
8”
6
1
/
16”
16 
15
/
16”
27 
7
/
8”
42
18 
3
/
16”
26 
3
/
16”
6
166
170
SH20N50
17 
15
/
16”
25 
15
/
16”
27 
3
/
8”
6
1
/
16”
16 
15
/
16”
27 
7
/
8”
42
18 
3
/
16”
26 
3
/
16”
6
171
175
SH24N20
17 
15
/
16”
25 
15
/
16”
27 
3
/
8”
6
1
/
16”
16 
15
/
16”
27 
7
/
8”
42
18 
3
/
16”
26 
3
/
16”
6
180
185
(A)