For the most efficient and quiet operation:
Use no more than three 90° elbows.
Make sure there is a minimum of 24" (61 cm) of straight vent 
between the elbows if more than 1 elbow is used.
Do not install 2 elbows together.
Use clamps or duct tape to seal all joints in the vent system.
The vent system must have a damper. If roof or wall cap has a 
damper, do not use damper supplied with the range hood.
Use caulking to seal exterior wall or roof opening around the 
cap.
Cold Weather Installations
An additional back draft damper should be installed to minimize 
backward cold air flow and a thermal break should be installed to 
minimize conduction of outside temperatures as part of the vent 
system. The damper should be on the cold air side of the thermal 
break.
The break should be as close as possible to where the vent 
system enters the heated portion of the house.
Makeup Air
Local building codes may require the use of makeup air systems 
when using ventilation systems greater than specified CFM of air 
movement. The specified CFM varies from locale to locale. 
Consult your HVAC professional for specific requirements in your 
area.
Venting Methods
Vent system can terminate either through the roof or wall. Use 
3
¹⁄₄" x 10" (8.3 x 25.4 cm) rectangular with a maximum vent 
length of 35 ft (10.7 m) or 7" (17.8 cm) or larger round vent with a 
maximum length of 50 ft (15.2 m) for vent system.
NOTE: Flexible vent is not recommended. Flexible vent creates 
both back pressure and air turbulence that greatly reduce 
performance. 
Calculating Vent System Length
To calculate the length of the system you need, add the 
equivalent feet (meters) for each vent piece used in the system. 
7" (17.8 cm) Round Vent System
Example vent system
Roof Venting
Wall Venting
A. 7" (17.8 cm) round vent 
through roof 
(purchased separately). 
3
¹⁄₄" x 10" (8.3 x 25.4 cm) 
rectangular vent through the 
roof for series UXT30, UXT42 
and UXT52 (purchased 
separately).
B. Roof cap 
(purchased separately)
C. 18" (45.7 cm) min. to 
24" (61.0 cm) max. above the 
cooking surface. 
A. 7" (17.8 cm) round vent out the 
top and through the wall  
(purchased separately). 
3
¹⁄₄" x 10" (8.3 x 25.4 cm) 
rectangular vent through the 
wall or out the top for series 
UXT30, UXT42 and UXT52 
(purchased separately).
B. Wall cap 
(purchased separately)
C. 18" (45.7 cm) min. to 
24" (61.0 cm) max. above the 
cooking surface. 
A
B
C
A
B
C
Vent Piece
Round
45° elbow
2.5 ft
(0.8 m) 
90° elbow
5.0 ft
(1.5 m)
7" (17.8 cm) wall cap
0.0 ft
(0.0 m)
3
¹⁄₄" x 10" (8.3 cm x 25.4 cm) 
to 7" (17.8 cm)
4.5 ft
(1.4 m)
3
¹⁄₄" x 10" (8.3 cm x 25.4 cm) 
to 7" (17.8 cm) 90° elbow
5.0 ft
(1.5 m)
Maximum Recommended Length
= 50 ft (15.2 m)
1 - 90° elbow
= 5.0 ft (1.5 m)
1 - wall cap
= 0.0 ft (0.0 m)
8 ft (2.4 m) straight
= 8.0 ft (2.4 m)
Length of 7" (17.8 cm) system
= 13.0 ft (3.9 m)
Wall cap
 
 
 
 
7" (17.8 cm) round
90˚ elbow
2 ft (0.6 m)
6 ft (1.8 m)