9. TROUBLESHOOTING 
 
9.3 Remedies for warnings 
CAUTION 
If an absolute position counter warning (AL.E3) occurred, always to make home 
position setting again. Not doing so may cause unexpected operation. 
 
 
POINT 
 
When any of the following alarms has occurred, do not resume operation by 
switching power of the servo amplifier OFF/ON repeatedly. The servo amplifier 
and servo motor may become faulty. If the power of the servo amplifier is switched 
OFF/ON during the alarms, allow more than 30 minutes for cooling before 
resuming operation. 
Excessive regenerative warning (AL.E0) 
Overload warning 1 (AL.E1) 
 
 
If AL.E6 or AL.EA occurs, the servo off status is established. If any other warning occurs, operation can be 
continued but an alarm may take place or proper operation may not be performed. 
Remove the cause of warning according to this section. Use the MR Configurator to refer to a factor of warning 
occurrence. 
 
Display Name 
Definition 
Cause 
Action 
AL.92 Battery 
cable 
disconnection 
warning 
Absolute position 
detection system battery 
voltage is low. 
1. Battery cable is open. 
Repair cable or changed. 
 
2. Battery voltage supplied from the servo 
amplifier to the encoder fell to about 3V 
or less. 
(Detected with the encoder) 
Change the battery. 
 
 
 
3. An encoder cable is broken. 
Repair or replace the encoder 
cable. 
AL.96 Home 
position 
setting warning 
Home position setting 
could not be made. 
1. The position is out of in-position range 
at the home position setting. 
Set the home position within the 
in-position range. 
 
 
 
2. A command pulse is input during the 
home position setting. 
Input the command pulse after 
the home position setting. 
 
 
 
3. Creep speed high. 
Reduce creep speed. 
AL.99 Stroke 
limit 
warning 
The stroke end (LSP or 
LSN) of the direction 
which gave instructions 
was turned off. 
The forward rotation stroke end (LSP) is 
turned off at the forward rotation 
command. 
Review the moving range to 
avoid turning off LSP/LSN. 
 
 
The reverse rotation stroke end (LSN) is 
turned off at the reverse rotation 
command. 
 
AL.9F  Battery warning 
Voltage of battery for 
absolute position detection 
system reduced. 
Battery voltage fell to 3.2V or less. 
(Detected with the servo amplifier) 
Change the battery. 
AL.E0 Excessive 
regenerative 
warning 
There is a possibility that 
regenerative power may 
exceed permissible 
regenerative power of 
built-in regenerative 
resistor or regenerative 
option. 
Regenerative power increased to 85  or 
more of permissible regenerative power of 
built-in regenerative resistor or 
regenerative option. 
<Checking method> 
Call the status display or MR 
Comfigurator, and check regenerative 
load ratio. 
1. Reduce frequency of 
positioning. 
2. Change the regenerative 
option for the one with larger 
capacity. 
3. Reduce load. 
4. Replace the servo amplifier/ 
servo motor with one of larger 
capacity.