12. OPTIONS AND AUXILIARY EQUIPMENT
 
12.3.3 Connection example 
POINT 
 
Connecting PR terminal of the brake unit to P terminal of the servo amplifier results 
in brake unit malfunction. Always connect the PR terminal of the brake unit to the 
PR terminal of the resistor unit. 
 
 
(1) Combination with FR-BR-(H) resistor unit 
(a) When connecting a brake unit to a servo amplifier 
P(    )
N(    )
MC
NFB
RA1
ALM
Servo motor
thermal relay
RA2
(Note 8)
(Note 1)
Power 
supply
N/
P/
BUE
SD
PR
B
C
A
SD
MSG
(Note 4)
(Note 7)
P
1
P
2
C
FR-BU2-(H)
FR-BR-(H)
Servo amplifier
P
PR
TH2
TH1
(Note 6)
(Note 5)
(Note 3)
(Note 2)
(Note 9)
L
1
L
2
L
3
L
11
L
21
(Note 10)
CN1
21
DICOM
48
ALM
20
DICOM
46
DOCOM
42
EMG
15
SON
Plate SD
24VDC
RA1
(Note 11)
OFF
MC
ON
MC
Emergency
stop
(Note 11)
SK
 
Note 1. For power supply specifications, refer to section 1.3. 
2. For the servo amplifier of 5k and 7kW, always disconnect the lead of built-in regenerative resistor, which is connected to the P 
and C terminals. For the servo amplifier of 11k to 22kW, do not connect a supplied regenerative resistor to the P and C 
terminals. 
3. Always connect P
1
 and P
2
 terminals (P
1
 and P for the servo amplifier of 11k to 22kW) (Factory-wired). When using the power 
factor improving DC reactor, refer to section 12.13. Use only one of power factor improving DC reactor or power factor 
improving AC reactor. 
4. Connect the P/  and N/  terminals of the brake unit to a correct destination. Incorrect connection results in servo amplifier 
and brake unit malfunction.  
5. For 400VAC class, a step-down transformer is required. 
6. Contact rating: 1b contact, 110VAC_5A/220VAC_3A 
    Normal condition: TH1-TH2 is conducting. Abnormal condition: TH1-TH2 is not conducting. 
7. Contact rating: 230VAC_0.3A/30VDC_0.3A 
    Normal condition: B-C is conducting/A-C is not conducting. Abnormal condition: B-C is not conducting/A-C is conducting.  
8. For the servo amplifier of 11kW or more, connect the thermal relay censor of the servo amplifier. 
9. Do not connect more than one cable to each P( ) and N( ) terminals of the servo amplifier. 
10. Always connect BUE and SD terminals (Factory-wired). 
11. Configure the circuit to shut down the main circuit power supply simultaneously with the turn off of emergency stop (EMG) 
using the external sequence.