12. OPTIONS AND AUXILIARY EQUIPMENT
12.5 Power regenerative common converter
POINT
Use the FR-CV for the servo amplifier of 200V class and the FR-CV-H for that of
400V class.
For details of the power regenerative common converter FR-CV-(H), refer to the
FR-CV-(H) Installation Guide (IB(NA)0600075).
Do not supply power to the main circuit power supply terminals (L
400V class.
For details of the power regenerative common converter FR-CV-(H), refer to the
FR-CV-(H) Installation Guide (IB(NA)0600075).
Do not supply power to the main circuit power supply terminals (L
1
, L
2
, L
3
) of the
servo amplifier. Doing so will fail the servo amplifier and FR-CV-(H).
Connect the DC power supply between the FR-CV-(H) and servo amplifier with
correct polarity. Connection with incorrect polarity will fail the FR-CV-(H) and servo
amplifier.
Two or more FR-CV-(H)'s cannot be installed to improve regeneration capability.
Two or more FR-CV-(H)'s cannot be connected to the same DC power supply line.
Connect the DC power supply between the FR-CV-(H) and servo amplifier with
correct polarity. Connection with incorrect polarity will fail the FR-CV-(H) and servo
amplifier.
Two or more FR-CV-(H)'s cannot be installed to improve regeneration capability.
Two or more FR-CV-(H)'s cannot be connected to the same DC power supply line.
When using the power regenerative common converter, set parameter No.PA02 to "
01".
(1) Model
Symbol
Voltage class
None
200VAC class
H
400VAC class
Symbol
Capacity [kW]
7.5k
7.5
11k
11
15k
15
22k
22
30k
30
37k
37
55k
55
Capacity
(2) Selection
The power regenerative common converter FR-CV can be used for the servo amplifier of 200VAC class
with 750 to 22kW and that of 400VAC class with 11k to 22kW. The following shows the restrictions on using
the FR-CV-(H).
with 750 to 22kW and that of 400VAC class with 11k to 22kW. The following shows the restrictions on using
the FR-CV-(H).
(a) Up to six servo amplifiers can be connected to one FR-CV-(H).
(b) FR-CV-(H) capacity [W] Total of rated capacities [W] of servo amplifiers connected to FR-CV-(H).
(c) The total of used servo motor rated currents should be equal to or less than the applicable current [A] of
the FR-CV-(H).
(d) Among the servo amplifiers connected to the FR-CV-(H), the servo amplifier of the maximum capacity
should be equal to or less than the maximum connectable capacity [W].