12. OPTIONS AND AUXILIARY EQUIPMENT
 
12.11 Selection example of wires 
POINT 
 
Wires indicated in this section are separated wires. When using a cable for power 
line (U, V, and W) between the servo amplifier and servo motor, use a 600V grade 
EP rubber insulated chloroprene sheath cab-tire cable (2PNCT). For selection of 
cables, refer to appendix 6. 
To comply with the UL/CSA Standard, use the wires shown in appendix 10 for 
wiring. To comply with other standards, use a wire that is complied with each 
standard. 
Selection condition of wire size is as follows. 
Construction condition: One wire is constructed in the air 
Wire length: 30m or less 
 
 
(1) Wires for power supply wiring 
 
POINT 
 
Always use the 600V grade heat-resistant polyvinyl chloride insulated wire (HIV 
wire) when using the HF-JP series servo motor. 
 
 
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent. 
C
P
U
V
W
L
11
L
21
U
V
W
L
1
L
2
L
3
B1
B2
1) Main circuit power supply lead
Servo amplifier
3) Motor power supply lead
Servo motor
Power supply
Motor
Electro-
magnetic 
brake
Encoder
4) Electromagnetic 
    brake lead
Encoder cable
2) Control power supply lead
(Note)
C
P
N
4) Regenerative option lead
Regenerative option
Cooling fan
BU
BV
BW
6) Cooling fan lead
Power supply
7) Thermal
OHS1
OHS2
Thermal
8) Power regenerative 
    converter lead
Power regenerative 
converter
 
Note. There is no L
3
 for 1-phase 100 to 120VAC power supply.