2. INSTALLATION 
 
2.5 Parts having service lives 
The following parts must be changed periodically as listed below. If any part is found faulty, it must be changed 
immediately even when it has not yet reached the end of its life, which depends on the operating method and 
environmental conditions. For parts replacement, please contact your local sales office. 
 
Part name 
Life guideline 
Servo amplifier 
Smoothing capacitor 
10 years 
Relay 
Number of power-on and number of emergency 
stop times : 100,000 times 
Cooling fan 
10,000 to 30,000hours (2 to 3 years) 
Absolute position battery 
Refer to section 14.2 
 
(1) Smoothing capacitor 
Affected by ripple currents, etc. and deteriorates in characteristic. The life of the capacitor greatly depends 
on ambient temperature and operating conditions. The capacitor will reach the end of its life in 10 years of 
continuous operation in normal air-conditioned environment (40  (104 ) surrounding air temperature or 
less). 
 
(2) Relays 
Their contacts will wear due to switching currents and contact faults occur. Relays reach the end of their life 
when the cumulative number of power-on and emergency stop times is 100,000, which depends on the 
power supply capacity. 
 
(3) Servo amplifier cooling fan 
The cooling fan bearings reach the end of their life in 10,000 to 30,000 hours. Normally, therefore, the 
cooling fan must be changed in a few years of continuous operation as a guideline. 
It must also be changed if unusual noise or vibration is found during inspection.