15. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW) 
 
15.6.2 Drive unit 
POINT 
 
Explanation made in this section is exclusively for the driver unit. 
Other troubleshooting is the same as that for servo amplifiers with 22kW or less. 
Refer to chapter 9. 
As soon as an alarm occurs, make the Servo off status and interrupt the main 
circuit power. 
 
 
(1) Alarms and warning list 
When an error occurs during operation, the corresponding alarm or warning is displayed. If any alarm or 
warning has occurred, refer to (2) or (3) in this section and take the appropriate action. When an alarm 
occurs, the ALM turns OFF. 
After its cause has been removed, the alarm can be deactivated in any of the methods marked in the alarm 
deactivation column. The alarm is automatically canceled after removing the cause of occurrence. 
 
 
Display 
(Note)Alarm code 
Name 
Alarm deactivation 
 
Display 
Name 
CN1 
22 
(bit 2) 
CN1 
23 
(bit 2) 
CN1 
24 
(bit 0) 
Power 
OFF   ON 
Error reset 
CPU  reset 
Alarms 
AL.9C 
Converter 
warning 
Alarms AL.1B 
Converter 
alarm 
 
 
 
AL.E9 
Main circuit off 
warning 
Note. 0: OFF 
1: ON 
 
 
 
 
 
 
 
 
 
 
 
 
(2) Remedies for alarms 
 
CAUTION 
When any alarm has occurred, eliminate its cause, ensure safety, then reset the 
alarm, and restart operation. Otherwise, injury may occur. 
 As soon as an alarm occurs, mark servo-off and power off the main circuit and 
control circuit. 
 
 
POINT  
The alarm can be deactivated by switching power off, then on. For details, refer 
to (1) in this section. 
 
 
If an alarm occurs, the trouble (ALM) turns off and alarm number is displayed in the display area. 
The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. MR 
Configurator may be used to refer to the cause the alarm. 
 
Display Name 
Definition 
Cause 
Action 
AL.1B Converter 
alarm 
An alarm occurred in the 
converter unit during servo 
on. 
1. An alarm occurred in the converter 
unit during servo on. 
Check the alarm of the converter 
unit, and take the action following 
the remedies for alarms of the 
converter unit. (Refer to section 
15.6.1 (2).) 
2. The protection coordination cable or 
terminal connector is not correctly 
connected. 
Connect correctly.