15. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW) 
 
15.8.2 Power supply equipment capacity and generated loss 
POINT 
 
The calculation method of heat dissipation area for enclosed control panel is the 
same as that for servo amplifiers with 22kW or less. Refer to section 11.2 (2). 
 
 
Table 15.1 indicates the generated loss and power supply capacity under rated load per combination of the 
converter unit and drive unit. When the servo motors is run at less than the maximum speed, the power supply 
equipment capacity is lower than the value in the table but the heat generated does not change. 
Since the servo motor requires 2 to 2.5 times greater instantaneous power for acceleration, use the power 
supply which ensures that the voltage lies within the permissible voltage fluctuation at the main circuit power 
supply terminals (L
1
, L
2
, L
3
) of the converter unit. The power supply equipment capacity changes with the 
power supply impedance. 
The actually generated heat falls within the ranges at rated torque and at zero torque according to the 
frequencies of use during operation. When designing an enclosed control box, use the values in the table, 
considering the worst operating conditions. The generated heat in Table 15.1 does not include heat produced 
during regeneration. 
 
Table 15.1 Power supply capacity and generated heat per servo amplifier at rated output 
 
Converter unit 
Drive unit 
Servo motor 
Power supply 
capacity [kVA] 
(Note) 
Drive unit-generated heart[W] 
Area required 
for heat 
dissipation 
[m
2
Power factor 
improving DC 
reactor is not 
used 
Power factor 
improving DC 
reactor is used
At rated torque  At zero torque 
MR-J3-CR55K 
MR-J3-DU30KA
HA-LP30K1 
HA-LP30K1M 
HA-LP30K2 
48 40 
1550(1100 450)  
31.0 
MR-J3-DU37KA
HA-LP37K1 
HA-LP37K1M 
HA-LP37K2 
59 49 
1830(1280 550)  
36.6 
MR-J3-CR55K4 
MR-J3-
DU30KA4 
HA-LP25K14 40 
35 1080(850 230)  
21.6 
HA-LP30K14 
HA-LP30K1M4 
HA-LP30K24 
48 40 
1290(1010 280) 60 
(30 30) 25.8 
MR-J3-
DU37KA4 
HA-LP37K14 
HA-LP37K1M4 
HA-LP37K24 
59 49 
1542(1200 342)  
30.8 
MR-J3-
DU45KA4 
HA-LP45K1M4 
HA-LP45K24 
71 59 
1810(1370 440)  
36.2 
MR-J3-
DU55KA4 
HA-LP50K1M4 80 
67 2120(1650 470)  
42.4 
HA-LP55K24 87 
72 
2150(1650 500)  
43.0 
Note. The heat generated by the drive unit is indicated in the left term within the parentheses, and the heat generated by the converter 
unit in the right term.