16. PARAMETER UNIT (MR-PRU03) 
 
16.5.4 Alarm/diagnostic mode 
(1) Alarm display 
The flowchart below shows the procedure of settings involving alarms, alarm history, external I/O signal 
(DIDO) display, device and diagnosis. 
ALM/
DGN
STOP
RESET
Alarm
Current alarm
(When undervoltage (AL.10) occurred.)
Alarm history
Motor information
Total power-on time
I/O display
Diagnosis
Software number
When parameter error (AL.37) 
occurred.
The alarm number of the current 
alarm is displayed. 
This screen is displayed once an 
alarm occurred regardless of the 
display mode selected.
Alarms are reset by the error 
reset command. Press the 
"1" key to execute, or the "0" 
key to cancel.
For six alarms including the latest alarm and 
five other alarms in alarm history (0 to 5), their 
alarm numbers and energization time elapsed 
before the alarm occurrence are displayed.
The alarm history can be cleared. (Refer to (2) 
in this section.) 
ON/OFF status of DIDO is displayed.
     : ON
     : OFF
The parameter No. of the erroneous parameter is displayed 
when parameter error (AL.37) occurred.
The software number is displayed.
The motor information is displayed.
The total power-on time (P-on) and the number of power-on 
times (SW.) since shipped are displayed.
Automatic VC offset
The automatic VC offset contents are displayed.