3. SIGNALS AND WIRING 
 
3.3 Explanation of power supply system 
3.3.1 Signal explanations 
POINT 
 
For the layout of connector and terminal block, refer to outline drawings in 
chapter 10. 
 
 
Abbreviation 
Connection target 
(application) 
Description 
L
1
 
L
2
 
L
3
 
 
Supply the following power to L
1
, L
2
, L
3
. For the 1-phase 200 to 230VAC power supply, connect 
the power supply to L
1
, L
2
, and keep L
3
 open. 
 
 
 
Servo amplifier
Power supply 
MR-J3-10A to 
70A 
MR-J3-100A 
to 22KA 
MR-J3-10A1 
to 40A1 
 
 
 
3-phase 200 to 230VAC, 50/60Hz 
 
L
1
L
2
L
3
 
 
 
Main circuit power   
1-phase 200 to 230VAC, 50/60Hz 
L
1
L
2
 
 
 
 
supply 
 
1-phase 100 to 120VAC, 50/60Hz 
 
 
L
1
L
2
 
 
 
   
 
 
 
 
 
 
Servo amplifier
Power supply 
MR-J3-60A4 to 22KA4 
 
 
 
3-phase 380 to 480VAC, 50/60Hz 
 
L
1
L
2
L
3
 
 
 
 
   
 
 
 
 
P
1
 
P
2
 
Power factor 
improving DC 
reactor 
1) MR-J3-700A or less 
When not using the power factor improving DC reactor, connect P
1
 and P
2
. (Factory-wired.) 
When using the power factor improving DC reactor, disconnect P
1
 and P
2
, and connect the 
power factor improving DC reactor to P
1
 and P
2
2) MR-J3-11KA(4) to 22KA(4) 
MR-J3-11KA(4) to 22KA(4) do not have P
2
When not using the power factor improving reactor, connect P
1
 and P. (Factory-wired) 
When using the power factor improving reactor, connect it to P and P
1
Refer to section 12.13. 


Regenerative 
option 
1) MR-J3-350A or less MR-J3-200A4 or less 
When using servo amplifier built-in regenerative resistor, connect P( ) and D. (Factory-wired)
When using regenerative option, disconnect P( ) and D, and connect regenerative option to 
P and C. 
2) MR-J3-350A4 500A(4) 700A(4) 
MR-J3-350A4 500A(4) 700A(4) do not have D. 
When using servo amplifier built-in regenerative resistor, connect P and C. (Factory-wired) 
When using regenerative option, disconnect P and C, and connect regenerative option to P 
and C. 
3) MR-J3-11KA(4) to 22KA(4) 
MR-J3-11KA(4) to 22KA(4) do not have D. 
When not using the power regenerative converter and the brake unit, make sure to connect 
the regenerative option to P and C. 
Refer to section 12.2 to 12.5. 
L
11
 
L
21
 
Control circuit 
power supply 
Supply the following power to L
11
L
21.
 
 
 
Servo amplifier
Power supply 
MR-J3-10A to 
22KA 
MR-J3-10A1 
to 40A1 
MR-J3-60A4 
to 22KA4 
 
 
1-phase 200 to 230VAC, 50/60Hz 
L
11
L
21
 
 
 
 
 
1-phase 100 to 120VAC, 50/60Hz 
 
L
11
L
21
 
 
 
 
1-phase 380 to 480VAC, 50/60Hz 
 
 
L
11
L
21