Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–30
It is possible for the inverter to retain the frequency set from the [UP] and [DWN] termi-
nals through a power loss. Parameter C101 enables/disables the memory. If disabled, the 
inverter retains the last frequency before an UP/DWN adjustment. Use the [UDC] 
terminal to clear the memory and return to the original set output frequency.
Option 
Code
Terminal 
Symbol
Function Name
Input 
State
Description
27
UP
Remote Control 
UP Function (motor-
ized speed pot.)
ON
Accelerates (increases output frequency) motor 
from current frequency
OFF
Output to motor operates normally
28
DWN
Remote Control 
DOWN Function 
(motorized speed 
pot.)
ON
Decelerates (decreases output frequency) motor 
from current frequency
OFF
Output to motor operates normally
29
UDC
Remote Control Data 
Clear
ON
Clears the Up/down frequency memory
OFF
No effect on Up/down memory
Valid for inputs:
C001, C002, C003, C004, 
C005
Required settings:
A001 = 02
Notes:
This feature is available only when the frequency 
command source is programmed for operator 
control. Confirm A001 is set to 02.
This function is not available when [JG] is in use.
The range of output frequency is 0 Hz to the value 
in A004 (maximum frequency setting).
The minimum ON time of [UP] and [DWN] is 50 ms.
This setting modifies the inverter speed from using F001 output frequency setting as a starting point.
Example (requires input configuration—
see page 
See I/O specs on page 
.
DWN UP
1
2
3
4
5