"UniVert 2" inverter 
 
Page 19 of 42 
8000012364 BAL, en 
Switches S2.4, S2.5 and S2.6: Own Address (INV) 
The settings must be different on all INVs! 
Standard setting: 
Address 1: S2.4, S2.5 and S2.6 open 
 
 
S2.4 S2.5 S2.6 
Address 1 
0 0 0 
Address 2 
0 0 1 
Address 3 
0 1 0 
Address 4 
0 1 1 
Address 5 
1 0 0 
Address 6 
1 0 1 
Address 7 
1 1 0 
Address 8 
1 1 1 
 
 
 
ATTENTION:  
With parallel operation systems, the addresses set must not exceed the 
number of parallel INVs in the system; for example, in a system with 
2 parallel inverters only address 1 or 2 may be set. Addresses 3 or 4 
are then only permissible for individually operated INVs!
 
 
Switches S2.7 and S2.8: Number of redundant INVs 
 
 
S2.7 S2.8 
0 INVs 
0 0 
1 INV 
0 1 
2 INVs 
1 0 
3 INVs 
1 1 
 
The settings must be the same on all INVs and the SBS! 
Standard setting: S2.7 and S2.8 open 
 
Example: 4 INVs are in the system, at least 3 INVs should run, 
i.e. 1 INV is redundant: S2.1=0; S2.2=1; S2.3=1; S2.7=0; S2.8=1