Heatcraft Refrigeration Products H-IM-79E Manual De Usuario

Descargar
Página de 36
22
System Defaults
Table 2. System Defaults
 PARAMETERS
CODE
AIR
ELECTRIC
 
Refrigerant 
rEF 
R-22 
R-404A
 
Box Temperature 
bot 
35°F 
-10°F
 
Superheat 
SUP 
8°F 
8°F
 
Slave Evaporator 
SLA 
No 
No
 
No. of Defrost per Day 
dFn 
4   
 
Defrost Fail-safe time 
dFF 
40 min. 
30 min.
 
Defrost End Temperature 
dFt 
45°F 
60°F
 
Defrost Delay Start Time 
dFS  
0 hrs. 
0 hrs.
 
Alarm High Temperature 
ALH  
50°F 
5°F
 
Alarm Low Temperature 
ALL 
30°F 
-15°F
 
Alarm Time 
ALt 
60 min. 
60 min.
 
Temperature Units 
F-C 
°F  
°F
Table 1. Resistance/Temperature Specification
 Temperature °F
Ohms
Temperature °F
Ohms
 
104 
5,320 
32 
32,650
 
86 
8,060 
23 
42,330
 
77  
10,000 
14 
55,330
  
68 
12,490  
 5 
72,950
 
59 
15,710 
 -4 
97,070
 
50 
19,900 
-13 
130,410
  
41 
25,400 
 -22 
176,960