Heatcraft Refrigeration Products H-IM-79E Manual De Usuario

Descargar
Página de 36
6
Each Beacon II board power is supplied by a transformer in the evaporator on which  
it is mounted. Do not run any 24 VAC wires between Beacon II boards on the evaporators.
Configuration
CU
M
S
S
S
M = Master Evaporator 
S = Slave Evaporator 
CU = Condensing Unit
If there are multiple evaporators on a system, the 
program for each SLAVE evaporator must be changed to 
identify it as a SLAVE. To do so, press the “
PROGRAM
REVIEW” button repeatedly until “SLA” appears then 
use the “
SELECT” knob to select “YES” then press 
ENTER”. All Beacon II boards are shipped with the 
factory default as a MASTER evaporator. Place all 
boards in the “
SERVICE” mode while you program the 
setpoints to avoid errors and alarms which may cause 
troubles at startup.
VERY IMPORTANT: This must be done for each slave 
board.
Multiple Evaporator Configuration (Master/slave)
Up to 4 evaporators can be connected as a  
master/slave configuration. 
DO NOT remove the room
sensor from any of the Beacon II boards.  
 
This also applies when connected to the optional Smart 
Controller.
PROGRAM
REVIEW
SELECT