Air Defrost Sequence of Operation
for Coolers
Air defrost units are preprogrammed for 3 hours of 
compressor run time between defrosts. These periods are 
not reprogrammable. After 3 hours, the temperature control 
will turn the compressor off. When the coil temperature 
reaches 38°F, the control will terminate the defrost cycle. 
Room Thermostat Settings:
• Approximate dial settings of control 
  0 = Unit off (not an electrical disconnect)
  1 = 52°F (11°C)
  2 = 49°F (9°C)
  3 = 45°F (7°C)
  4 = 41°F (5°C)
  5 = 38°F (3°C)
  6 = 34°F (1°C)
Cooler Defrost Control
Cooler units utilize an electronic temperature control. 
The temperature may be adjusted by setting the dial. This 
control is preset to provide 3 hours of compressor run time 
between defrost cycles. Defrosts are temperature terminated 
and cannot be reprogrammed. The temperature control 
is programmed for minimum on cycle of one minute and 
minimum off cycle of four minutes.
Maintenance
The evaporator section of a 
 system should be checked 
at least once for proper defrosting because the amount 
and pattern of frosting can vary greatly. The frost build-up 
is dependent on the temperature of the room, the type of 
product being stored, how often new product is brought 
into the room and percentage of time the door to the room 
is open.
System Standard Maintenance Guidelines
After first year of operation and under normal usage, 
maintenance should cover the following items at least once 
every six months:
  1.  Check and Tighten ALL electrical connections.
  2.  Check all wiring and insulators.
  3.  Check contactors for proper operation and for worn  
    contact points.
  4.  Check all fan motors. Tighten motor mount bolts/nuts  
    and tighten fan set screws.
  5.  Clean the condenser coil surface.
  6.  Check the operation of the control system. Make  
    certain all safety controls are operating properly.
  7.  Check that all defrost controls are functioning properly.
  8.  Clean the evaporator coil surface.
  9.  Clean the drain pan and check the drain pan and  
    drain line for proper drainage.
All Cooler Models
NOTE:  If power is interrupted to the unit during the 
refrigeration off-cycle (system at temperature setpoint, 
compressor off), the thermostat will initiate an extra defrost 
period approximately one hour after power is restored.