APPLICATION
Model OFSD-212 is an ‘out of the wall’ high performance combina-
tion fire smoke damper with 3V style blades. OFSD-212 is approved 
for use in walls, partitions, and floors with fire resistance ratings less 
than 3 hours. Removal of wall grille allows access to actuator and 
other components. This model's operational ratings of 2000 fpm (10.2 
m/s) and pressures to 4 in. wg (1 kPa). OFSD-212 shall be installed 
vertically (with blades running horizontal) or horizontally and is rated 
for airflow and leakage in either direction.
Ratings
UL555 Fire Resistance Rating:
 
Fire Rating:  
1
1
2
 
hours in walls  
 
Dynamic Closure Rating:  Actual ratings are size dependent 
 
Max. Velocity:  
2000 fpm (10.2 m/s) 
 
Max. Pressure:  
4 in. wg (1 kPa) - differential 
 
 
pressure
UL555S Leakage Rating:
 
Leakage Class: 
II 
 
Operational Rating: 
Actual ratings are size dependent 
 
Max. Velocity: 
2000 fpm (10.2m/s) 
 
Max. Pressure: 
4 in. wg (1 kPa) 
 
Max. Temperature: 
350ºF (177ºC)- depending upon the 
 
 
actuator
STANdARd CONSTRuCTION
 
Frame:  
5 in. x 1 in. (127mm x 25mm) 
 
 
galvanized steel hat channel with 
 
 
reinforced corners. A low profile head 
 
 
and sill are used on sizes less than 
 
 
17 in. (432mm) high. 
 
Blades:  
16 ga. (1.5mm) galvanized steel, 
 
 
reinforced with 3 longitudinal 
 
 
structurally designed vee's. 
 
Seals: 
Extruded silicone rubber blade seals. 
 
 
Flexible stainless steel jamb seals 
 
Linkage: 
Concealed in jamb 
 
Closure device: 
UL listed 165°F (74ºC) RRL 
 
Axles: 
1
2
 in. (13mm) dia. plated steel  
 
Bearings: 
Bronze sleeve type 
 
Sleeve: 
Galvanized; wrapped with thermal 
 
 
blanket
 
Size Limitations:
 
Minimum Size:  
12 in. W x 12 in. H 
 
 
(305mm x 305mm) 
 
Maximum Size:  
Single section: 36 in. W x 36 in. H 
 
 
(914mm x 914mm)
Optional Features:
• POC retaining Angles 
• RRL/OCI (open closed indication switches) 
• 165ºF (74ºC), 212ºF (100ºC), 250ºF (121ºC), 350ºF (177ºC) RRL’s 
  available 
• TOR (remote override allows damper to perform smoke 
  management functions during fire emergency.) 
• Electric actuators  
• Momentary switch 
• Security bars 
• Sealed transition and sleeves
Model OFSd-212
Out Of Wall Combination FIRE SMOKE dAMPERS
Steel 3V Blades
UL 555S Leakage Class II
UL555 1
1
2
 Hour Fire Resistance Rating
Horizontal or Vertical Mount
“uL CLASSIFIEd (see complete marking on 
product)”
“uL CLASSIFIEd to Canadian safety standards 
(see complete marking on product)”
 
Standard 555 & 555S (Listing #R13317) 
* W & H dimensions furnished approximately ¼ in. (6mm) undersize.
  (Add blanket thickness (1⁄8 in.[3mm]) and sleeve thickness for overall 
sleeved damper dimension)
  Oversize wall opening as follows:
  Nominal damper size plus 3⁄8 in.(9.5mm) (see Page 6)
Model OFSD-212 meets the requirements for fire 
dampers, smoke dampers and combination fire 
smoke dampers established by:
National Fire Protection Association 
    NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC International Building Codes
ICBO  uniform Building Codes  
CSFM California State Fire Marshal 
  Fire Damper Listing (#3225-0981:103)
  Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
R
Greenheck Fan Corporation certifies that the 
model OFSD-212 shown herein is licensed to bear 
the AMCA Seal. The ratings shown are based on 
tests and procedures performed in accordance 
with AMCA Publication 511 and comply with the 
requirements of the AMCA Certified Ratings Pro-
grams. The AMCA Certified Ratings Seal applies to 
air performance ratings only.
Installation instructions available at www.greenheck.com