Greenheck Fan 468769 Prospecto

Descargar
Página de 1
Part  number 468769
 Drive Slip Breakaway Connection
Duct
Sleeve
S-slip
Top and Bottom
Duct to Sleeve Connection
4MFFWF
%VDU
7FSUJDBM4JEFT%VDU
UPTMFFWFDPOOFDUJPO
%SJWF4MJQ
Greenheck drive slip connections (S & Drive) are used on 
the side of the hemmed sleeves and the S-slip joints are 
used on the top and bottom. Standard drive slips are UL 
tested breakaway connections on dampers 20 in. (508mm) 
high and less. 
Installation
Greenheck Dampers may be supplied with factory hemmed 
20 ga. (1mm) sleeve for use with drive slip and s-slip joints. 
Sleeves and duct may be field hemmed by folding back the 
vertical sides a maximum of 1/2 in. (13mm) (as shown in 
Figure 1) to accommodate the 1 in. (25mm) wide drive slip. 
Join damper sleeve to duct at top and bottom sides using 
any  s-slip (See Figure 2).
Drive slip connection is used to connect the vertical sides 
of the damper sleeve to the duct. Cut a length of drive slip 
connection a maximum of 4 in. (102mm) longer than the 
vertical duct dimension. Guide the  drive slip connection 
onto the side members securing it over the hemmed edges 
until the connection extends beyond the top and bottom 
sides of the damper sleeve/ duct. The extra length should 
be hammered flat overlapping all four corners. 
Figure 2
Figure 3
Drive slip
Sleeve
S-slip
Duct
Figure 1
Copyright © 2007 Greenheck Fan Corporation
 #468769 Drive Slip Breakaway Connection Rev. 2  December 2007
“UL CLASSIFIED                                            
 (see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards                  
(see complete marking on product)”
Standards UL 555 & 555S
Classifications Filed at UL under Listing #R13317 
Refer to:
‘Installation Instructions for FD, DFD, SSFD, SSDFD, & 
KFD Series Curtain Fire Dampers’ (Part #452763) 
or
‘Installation Instructions for FD and DFD 150X Series 
Curtain Fire Dampers’ (Part #453946)
or
‘Installation, Operation and Maintenance Instructions 
for SMD-XXX, SESMD-XXX, SSSMD-XXX Series 
Smoke Dampers’ (Part #461338)
or
‘Installation, Operation and Maintenance Instructions 
for FSD-XXX, SSFSD-XXX, DFD-2XX, & CFSD-XXX 
Series Fire & Combination Fire Smoke Dampers’ (Part 
#461336) for additional details. 