SNMP Trap Number: 
Variable Trap 
No.
Description 
dupsCommunicationLost 
SEVER: Communication with the UPS failed 
dupsCommunicationEstablished 2 
INFORMATION: 
Communication with the UPS reestablished 
dupsPowerFail 
WARNING: Power failed! The UPS is operating on battery power 
dupsPowerRestored 
INFORMATION: Power restored! The utility power restored 
dupsLowBattery 
SEVER: The UPS batteries are low and will soon be exhausted 
dupsReturnFromLowBattery 
INFORMATION: The UPS has returned from a low battery condition 
dupsLoadWarning 
INFORMATION: Loading percent of the UPS over the Load Warning 
value 
dupsNoLongerLoadWarning 8 
INFORMATION: 
Returned from Load Warning condition 
dupsLoadSeverity 
Warning: Loading percent of the UPS over the Load Severity value 
dupsNoLongerLoadSeverity   
10 
INFORMATION: Returned from Load Severity condition 
dupsLoadOnBypass 
11 
WARNING: The UPS loads on bypass 
dupsNoLongerLoadOnBypass 12 
INFORMATION: The UPS is not on bypass mod 
dupsUPSFault 
13 
SEVER: A general fault caused in the UPS 
dupsBatteryGroundFault 
14 
SEVER: The UPS battery ground fault 
dupsNoLongerBatteryFault 15 
INFORMATION: 
The 
UPS recovered from battery ground fault 
dupsTestInProgress 16 
INFORMATION: The UPS test in progress 
dupsBatteryTestFail 
17 
SEVER: The UPS test in progress 
dupsFuseFailure 
18 
SEVER: The UPS fuse failed 
dupsFuseRecovered 19 
INFORMATION: The UPS fuse recovered 
dupsOutputOverload 
20 
SEVER: The UPS overload 
dupsNoLongerOverload 21 
INFORMATION: 
Recovered from UPS overload 
dupsOutputOverCurrent 
22 
SEVER: The UPS output is over current 
dupsNoLongerOutputOverCurrent 23 
INFORMATION: Recovered from UPS over current 
dupsInverterAbnormal 
24 
SEVER: The UPS inverter is operating abnormally 
dupsInverterRecovered 25 
SEVER: 
Recovered from UPS inverter abnormal state 
dupsRectifierAbnormal 
26 
SEVER: The UPS rectifier is operating abnormally 
dupsRectifierRecovered  
27 
INFORMATION: The UPS recovered from abnormal state 
dupsReserveAbnormal 
28 
SEVER: The UPS rectifier is operating abnormally 
dupsReserveRecovered 29 
INFORMATION: 
The 
UPS rectifier is now operating normally 
dupsLoadOnReserve 30 
INFORMATION: The UPS load on reserve 
dupsNoLongerLoadOnReserve 31 
INFORMATION: The UPS no longer load on reserve 
dupsEnvOverTemperature 
32 
WARNING: The environment is over normal temperature 
DupsNoLongerEnvOverTemperatu
re 
33 
INFORMATION: The environment recovered from abnormal 
temperatures 