7.  Circuit Overloading - Consideration should be given to the connection of the equipment 
to the supply circuit and the effect that overloading of the circuits might have on over 
current protection and supply wiring.  
8.  Reliable Grounding - Reliable grounding of Rackmounted equipment should be 
maintained. Particular attention should be given to supply connections other than direct 
connections to the branch circuit (e.g., use of power strips). 
9. 
All AC and DC versions are intended for use in a Restricted Access Location (RAL
). 
Wiring Instruction Guidelines for DC Module in 2DC and ACDC  
1.  Connection of a suitable grounding conductor to the grounding terminal at each 
power supply module (a minimum 14AWG copper conductor should be 
suitable based on a 15A circuit breaker requirement).  
2.  Connection of suitable supply wiring to the plus and minus terminals at each 
power supply module (a minimum 14AWG copper conductors is considered 
suitable based on the 11A input maximum).  The input terminal block at the 
power supply module is suitable for 22-14 AWG copper wire.  
3.  A suitable listed circuit breaker shall be provided in the building installation as 
the unit's disconnect device.  The branch circuit rating (i.e. minimum 15A listed 
circuit breaker, etc.). 
DC Power Supply Module Wiring Instructions 
The following diagram shows the wiring configuration for a -48 VDC power supply module for 
the 20-Slot Rackmount Chassis 2DC and ACDC. 
 
 
 
NOTE 
The chassis is protected against incorrect wiring configurations.  When wired incorrectly, the 
chassis will not function, but no damage will occur.