Programming Function Blocks and Features 
 
Video Recorder – User Manual 
 
94
Loop Menu Items  
Table 4-10 alphabetically describes every loop menu item. See Table 4-2 for additional prompts. 
Table 4-10   Loop Prompts 
 
 
Prompt 
Range/Selections 
Definition 
APPROACH HIGH 
Enter a value 0.1 to 100 or 
OFF. 
This function affects the process variable approach to set 
point when the process variable value is less than the set 
point value. The value entered is the percent of span 
deviation from set point at which a recalculation of the 
loop integral value will occur. Enter a starting value equal 
to the proportional band value (1/gain value) x 100 if Gain 
is used, or OFF at initial configuration. The value may be 
altered Online for final loop tuning. This function is useful 
for batch startup from a "cold" condition to control 
excessive overshoot when set point is reached. 
APPROACH LOW 
Enter a value 0.1 to 100 or 
OFF. 
Affects the process variable approach to set point when 
the process variable value is greater than the set point 
value. 
AUTO/MAN SELECT   OFF, discrete parameter, 0, 1 
This parameter takes the place of the Auto/Man button 
when the DISCR VS KEY SEL discrete is ON (1). 
AUTO/MAN SELECT = ON(1) = Manual mode 
AUTO/MAN SELECT = OFF (0) = Automatic mode 
When DISCR VS KEY SEL is OFF(0), AUTO/MAN SEL 
has no effect. 
CHG ACTION INPUT 
OFF, discrete parameter, 0, 1 
Change Action Input.  Selects the opposite control action 
from that selected for the control action (see CONTROL 
ACTION).  Control action is opposite when the discrete 
value is ON or "1". 
CONTROL ACTION 
Reverse (REV) or Direct (DIR) 
Acting Control. 
When Reverse Acting Control is selected, the loop output 
will increase as the process variable becomes less than 
set point, and will decrease as it becomes greater than 
the set point. When Direct Acting Control is selected, the 
output action is opposite. 
DISCR VS KEY SEL 
OFF, discrete parameter, 0, 1 
Discrete vs. Keyboard select.  When this discrete is ON 
(1), the Auto/Man and Set point buttons are disabled; their 
functioning is transferred to the AUTO/MAN SELECT and 
SETPOINT SELECT discretes.  See AUTO/MAN SELECT 
and SETPOINT SELECT.  Status changes made by 
AUTO/MAN SELECT and SETPOINT SELECT will remain 
when DISCR VS KEY SEL is OFF (0). 
DUAL TUNING SEL 
OFF, discrete parameter, 0, 1 
When ON(1), selects the second set of tuning constants 
(#2).  A bumpless transfer (integral term adjusted) 
calculation will be made on transition.