Programming Function Blocks and Features  
 
Video Recorder – User Manual 
 
105
4.11  Program Discrete Outputs 
Discrete Output function blocks control the relay or open collector output hardware.  The Program 
Discrete Outputs menu item will appear if a Discrete Outputs board is installed.  
 
ATTENTION 
If a discrete output has been assigned to a time proportioning output (DAT), it will not be programmable here.  
See "OUTPUT RELAY" in Table 4-13. 
 
Select a DO to program, then program the prompts in Table 4-15.  See Table 4-2 for additional prompts. 
Table 4-15   Discrete Output Prompts 
 
 
Prompt 
Range/Selections 
Definition 
ACTION STATE 
NORMAL, INVERT 
Determines whether the relay will normally be energized or 
de-energized when the DO’s Input is ON(1). To select 
energized when ON, enter NORMAL (not inverted). To select 
energized when OFF, enter INVERT (inverted). 
INPUT 
OFF, discrete parameter, 0, 
Source of the Discrete Output. 
EVENT ENABLE 
NONE, RISING, FALLING, 
BOTH 
Determines whether changes in DO’s status can be recorded 
as events in data storage.  For storage to occur, Data 
Storage must also be programmed to store Events. 
NONE - status changes are not stored 
RISING - OFF(0)-to-ON(1) changes can be stored 
FALLING - ON(1)-to-OFF(0) changes can be stored 
BOTH - Rising and falling changes can be stored