Programming Function Blocks and Features  
 
Video Recorder – User Manual 
 
109
Compare 
Compare can be used instead of an Alarm’s output to control a relay.  It can also provide on/off control 
with hysteresis. 
Compares 2 inputs.  Call the result of this comparison “Result”.  Result is a pulse that goes ON(1) when 
comparison is true, and OFF(0) when comparison is not true.  If hysteresis is given a value, then Result 
will not go OFF(0) until hysteresis value is exceeded.  Result is then processed according to the 
specified condition type and condition time.  The final output is a discrete pulse CVn OS. 
COMPARE
OPERATOR
&
HYSTERESIS
Input #1
Input #2
Result
CONDITION
TYPE
&
CONDITION
 TIME
CVn OS
 
Figure 4-2   Compare Signal Flow 
Table 4-19 and Table 4-20 describe the Compare prompts.  See Table 4-2 for additional prompts. 
Table 4-19  Compare Prompts 
 
 
Prompt 
Range/Selections 
Definition 
INPUT #1 
INPUT #2 
OFF, analog parameter, 
number 
Input sources to be compared. 
OPERATOR 
EQ, GT, LT, GTE, LTE, NEQ 
The Result will be set to ON(1) when the comparison is true: 
Input #1 OPERATOR  Input #2 
where OPERATOR is: 
EQ(=),  GT(>),  LT(<), GTE (
), LTE (
),  NEQ(
The Result will be set to OFF(0) when the comparison is false. 
HYSTERESIS 
Number, OFF 
Applies to all operators except EQ and NEQ.  If given a value, 
hysteresis determines when Result goes OFF(0) after the 
comparison becomes false. 
Operator Hysteresis 
Function 
GT:  
Result goes OFF when Input #2 - Input #1 
 Hyst
 
 
GTE:  
Result goes OFF when Input #2 - Input #1 > Hyst
 
 
LT:  
Result goes OFF when Input #1 - Input #2 
 Hyst
 
 
LTE:  
Result goes OFF when Input #1 - Input #2 > Hyst
 
 
See Figure 4-3. 
CONDITION TYPE 
NONE, DELAY, EXTEND, 
PULSE, RT PULSE 
See Table 4-20. 
CONDITION TIME 
OFF or number 
Enter number of seconds of condition time. See Table 4-20.