Honeywell VRX180 Manual De Usuario

Descargar
Página de 294
Programming Function Blocks and Features 
 
Video Recorder – User Manual 
 
118
Table 4-26   Logic Operators 
For this operator 
Definition 
if this is true 
then Result is 
AND 
If all programmed inputs are ON, 
Result is ON. 
All programmed inputs are 
ON(1) 
ON(1) 
OR 
If at least 1 programmed input is ON, 
Result is ON. 
At least 1 programmed 
input is ON(1) 
ON(1) 
XOR 
Uses Inputs A and B only. 
Input A is ON(1) and Input 
B is OFF(0). 
ON(1) 
 
If one and only one input is ON, Result 
is ON. 
Input A is OFF(0) and Input 
B is ON (1). 
ON(1) 
RESET/SET FF 
Rising edge of Input A turns Result 
ON. 
Input A is ON(1). 
ON(1) 
(Reset/Set Flip-Flop) 
Rising edge of Input B resets Result. 
Input A is OFF(0) and Input 
B is ON (1). 
OFF(0) 
Reset/Set FF
Input A
Input B
Result
 
TOGGLE/FF 
Toggle Flip-Flop.  Rising edge of Input 
A inverts Result 
Input A changes from 
OFF(0) to ON(1) (rising 
edge) 
ON(1) if it was 
OFF(0), or OFF(0) 
if it was ON(1). 
 
 
Input A changes from 
ON(1) to OFF(0) (falling 
edge) 
unchanged 
Input A
Toggle/Flip-Flop
Result
 
ONE SHOT 
Rising edge of Input A turns Result 
ON for one machine scan cycle. 
Input A is ON(1) for any 
length of time 
ON(1) for 1 scan 
cycle of the 
instrument, then 
OFF(0) 
Result
Input A
One Shot
 
PASS 
Passes Input A’s state unchanged to 
CONDITION TYPE. 
Input A changes state 
same as Input A