Rolling Average 
Outputs a rolling mean average CVn OV of the input over the specified Average Period.  As new input 
samples are collected, old samples are discarded.  The function will calculate a new average at equally 
spaced sample intervals. 
Sample interval = 
averaging period 
                                 # of samples
 
Rolling Average = 
sum of samples 
                                 # of samples
 
Example 
# of samples = 10 
Average Period = 30 minutes 
The first average will appear after 30 minutes, then will be updated every 30/10 or 3 minutes after. 
When the Reset Input is ON(1) all accumulated samples are discarded and the output is held until the 
Reset Input is OFF(0), then the averaging period resets. 
Table 4-46 describes the Rolling Average prompts. See Table 4-2 for additional prompts. 
 
Table 4-46   Rolling Average Prompts 
 
 
Prompt 
Range/Selections 
Definition 
RANGE LOW 
RANGE HIGH 
OFF or number 
Enter the output’s display limits.  Output is not clamped or 
flashed when it exceeds these limits. 
INPUT 
OFF, analog parameter, 
number 
This parameter will be averaged. 
RESET 
OFF, discrete parameter, 0, 1 
Resets average. 
# OF SAMPLES 
1-60 
Number of samples taken during average period. 
AVG PERIOD MINS 
OFF or number 
Number of minutes in average period.