Programming Function Blocks and Features  
 
Video Recorder – User Manual 
 
143
4.13 Program Alarms 
You can program an alarm to be triggered by any extreme input value. To program alarms, select 
“PROGRAM ALARMS” on the Main Program Menu.  Select an alarm to program. 
REFERENCE 
When an alarm occurs, it produces an output pulse which can be configured to trigger a discrete output (such 
as a relay). Refer to Section 4.11 for instructions. 
Table 4-50 describes the Alarm prompts. See Table 4-2 for additional prompts. 
Table 4-50   Alarm Prompts 
 
 
Prompt 
Range/Selections 
Definition 
ON STATE 
OFF STATE 
See Table 4-3 for 
choices. 
Enter labels for on and off states of alarm 
ALARM ACTION 
HIGH 
Alarm when input value 
 set point value. 
 LOW 
Alarm when input value 
 set point value. 
 
DEV 
Deviation. Alarm when input value deviates above or below compare 
point value by an amount 
 set point value. 
 HDEV 
High 
deviation 
 LDEV 
Low 
deviation 
 HRATE 
High Rate. Alarm when input value increases at rate 
 set point 
value, in units per minute. Negative rate set points are processed as 
positive values. May take up to 30 seconds to activate. 
 LRATE 
Low Rate. Alarm when input value decreases at rate 
 set point 
value, in units per minute. Negative rate set points are processed as 
positive values. May take up to 30 seconds to activate. 
 
NONE 
No alarm action. 
INPUT OFF, 
analog 
parameter, number 
Input source monitored by alarm. 
SETPOINT OFF, 
analog 
parameter, number 
Point at which alarm occurs. 
COMPARE 
POINT 
OFF, analog 
parameter, number 
DEV type only. It is the point against which the input point is 
compared. The difference between the input point and the compare 
point is the value which is measured against the alarm set point. 
HYSTERESIS 
OFF or number 
Hysteresis affects only the point at which an alarm clears. A high 
alarm will clear when the input is less than the set point minus the 
hysteresis value. A low alarm will clear when the input is greater than 
the set point plus the hysteresis value. A deviation alarm will clear 
when the input is less than the set point minus the hysteresis value. 
DELAY TIME 
OFF or number 
If the alarm condition clears before the delay time (in seconds) 
expires, no alarm will be indicated. Delay time must be in multiples of 
scan time. 
SAMPLE HOLD 
OFF, discrete 
parameter, 0 or 1 
When this parameter level = 1, the alarm processing is disable and 
the output is held.