Programming Function Blocks and Features 
 
Video Recorder – User Manual 
 
164
4.24 Scan Rate 
Scan rate is the time required to measure inputs, execute function blocks (AI, Loops, AO, DI, DO, CV, 
etc.) and update outputs.  It is also known as the machine cycle, scan cycle, and update rate. 
The Scan Rate prompt lets you set the scan rate of the instrument to a value slower than the maximum 
rate allowed by the hardware. The hardware will determine the default scan rate.  Allowable entries are 
250 milliseconds, 500 milliseconds, 1 second, 2 or 3 seconds.  250 ms rate is only available on 4 input 
units. 
We recommend the following scan rates for the following configurations. 
Table 4-70  Suggested Scan Rates 
Inputs 
Scan Rate 
W/Control 
Up to 4 
Up to 12 
Up to 16 
Up to 24 
Up to 32 
Up to 44 
Up to 48 
250 msec 
500 msec 
750 msec 
1 sec 
1.5 sec 
2.0 sec 
3.0 sec 
500 msec 
1 sec 
1 sec 
1.5 sec 
2 sec 
2 sec 
3 sec 
 
NOTE 
These are suggested scan rates.  In general, if your instrument responds too slowly, use a slower (higher) 
scan rate.  You can use a faster (lower) scan rate than suggested here, but be aware of possible sluggish 
display and button response time.