Setpoint Profiler 
 
Video Recorder – User Manual 
 
195
Table 5-5   Edit Profile Prompts (continued) 
Prompt 
Range/Selections 
Definition 
TIME MULTIPLIER 
Number 
Time Multiplier determines the speed at which 
the profiler will run when in Fast Forward mode.  
It is used for testing the profiler’s execution.  
See Fast Forward. 
When FAST FORWARD is ON(1), the profiler 
will run at a speed determined by the TIME 
MULTIPLIER parameter. 
Example 
The instrument is running at a 500msec scan 
rate.  The TIME MULTIPLIER is set to 60.  
Therefore the profiler will run in (500msec x 60) 
or 30 second increments. 
Running a profiler in FAST FORWARD is a way 
to check for proper functioning of the profiler’s 
events and outputs, without having to wait for 
the profiler to execute at its normal speed. 
See Figure 5-11.