Pretune Abort messages 
One of the following messages is displayed when an unusual event has aborted the pretune.  “PTA” 
means “Pretune Abort.” 
Table 7-14  Pretune Abort Messages 
 
Message 
Meaning/User action required 
PTA-WARM START 
A warm start occurred during pretune.  Repeat 
pretune. 
PTA-WENT OFFLINE 
Instrument went out of Online mode during pretune.  
Repeat pretune. 
PTA-LOOP STATUS 
Loop has PV that is bad (i.e. failed sensor) 
OR 
PV is a constant value such as from an upstream 
block in manual 
OR 
Loop has back calculation value from a downstream 
block that is bad or is the result of the downstream 
block being in manual. 
Repeat pretune. 
PTA-AM SEL CHNGE 
Loop switched between automatic and manual 
modes.  Repeat pretune. 
PTA-SP SEL CHNGE 
Loop was in automatic mode and an attempt was 
made to switch between Setpoint #1 and Setpoint #2.  
Repeat pretune. 
PTA-OUT MOVED 
Loop was in manual mode and loop’s output value 
changed.  Repeat pretune. 
PTA-SP MOVED 
Loop was in automatic mode and the setpoint value 
changed.  Repeat pretune. 
PTA-LOOP OS 
Loop is out of service.  Fix loop before repeating 
pretune. 
PTA-LOOP NOT CFG 
Loop is not configured.  Configure loop before 
repeating pretune. 
PTA-BAD STEP SIZ 
Step size is turned off.  Set step size to a value 
before repeating pretune.  See Table 7-11. 
PTA-ONOFF LOOP 
Cannot pretune an on/off type loop. 
PTA-BAD SN RATIO 
Increase step size. See Table 7-11. 
PTA-BAD OSC 
Repeat pretune with smaller gain or proportional 
band in loop. 
PTA-BAD ID VALUE 
Increase step size. See Table 7-11. 
PTA-DB ACCESS 
Unknown hardware problem.  Consult service. 
PTA-TASK FAIL 
Unknown hardware problem.  Consult service.