Honeywell VRX180 Manual De Usuario
Online Operation Using Menus
Video Recorder – User Manual
241
Pretune Abort messages
One of the following messages is displayed when an unusual event has aborted the pretune. “PTA”
means “Pretune Abort.”
means “Pretune Abort.”
Table 7-14 Pretune Abort Messages
Message
Meaning/User action required
PTA-WARM START
A warm start occurred during pretune. Repeat
pretune.
pretune.
PTA-WENT OFFLINE
Instrument went out of Online mode during pretune.
Repeat pretune.
Repeat pretune.
PTA-LOOP STATUS
Loop has PV that is bad (i.e. failed sensor)
OR
PV is a constant value such as from an upstream
block in manual
block in manual
OR
Loop has back calculation value from a downstream
block that is bad or is the result of the downstream
block being in manual.
block that is bad or is the result of the downstream
block being in manual.
Repeat pretune.
PTA-AM SEL CHNGE
Loop switched between automatic and manual
modes. Repeat pretune.
PTA-SP SEL CHNGE
Loop was in automatic mode and an attempt was
made to switch between Setpoint #1 and Setpoint #2.
Repeat pretune.
Repeat pretune.
PTA-OUT MOVED
Loop was in manual mode and loop’s output value
changed. Repeat pretune.
changed. Repeat pretune.
PTA-SP MOVED
Loop was in automatic mode and the setpoint value
changed. Repeat pretune.
changed. Repeat pretune.
PTA-LOOP OS
Loop is out of service. Fix loop before repeating
pretune.
pretune.
PTA-LOOP NOT CFG
Loop is not configured. Configure loop before
repeating pretune.
repeating pretune.
PTA-BAD STEP SIZ
Step size is turned off. Set step size to a value
before repeating pretune. See Table 7-11.
before repeating pretune. See Table 7-11.
PTA-ONOFF LOOP
Cannot pretune an on/off type loop.
PTA-BAD SN RATIO
Increase step size. See Table 7-11.
PTA-BAD OSC
Repeat pretune with smaller gain or proportional
band in loop.
band in loop.
PTA-BAD ID VALUE
Increase step size. See Table 7-11.
PTA-DB ACCESS
Unknown hardware problem. Consult service.
PTA-TASK FAIL