4. 
Suppress relay, contactor coils etc. using R-C, flywheel diode, or varistor 
suppressers fitted at the coils. 
Diode (DC Coils only) -
Good
Varistor - Better
Resistor/Capacitor -
Best
 
Figure 6-5 
Suppression of Contactor Coils 
5
Use screened or armoured cables for the power connections; ground the screen at 
both ends. 
Filter (Optional)
MICROMASTER
Screened or Armoured Cable - Grounded at both ends
Motor
 
Figure 6-6 
Use of Screened or Armoured Cables 
6
Consider using an RFI filter in the supply to the converter. 
 
Consider connecting the 0V of the inverter to the protective earth. This can often 
reduce noise in the 0V system.