MICROMASTER  Applications Handbook 
9.3 
Braking  Modules and Braking Resistors 
During regeneration (see section 8.2.2) it may be necessary to dissipate the 
energy that is returned to the inverter.  MICROMASTER MM420 units do not have 
the capability to dissipate regenerated energy. 
Some Siemens inverters have a built in ‘braking chopper’ and require only an 
external resistor to allow controlled dissipation.  The resistors can be supplied as 
optional parts to the inverters, and fit alongside the inverters.  They are specially 
designed to operate with the high voltages present in the DC link, and are of 
metalclad, IP54 design.  Braking resistors for operation with earlier 
MICROMASTERs were designed to mount underneath the inverters.  Other 
resistors can also be used, but care must be taken to ensure they are of adequate 
voltage and power rating. 
9.4 EMC 
Filters 
MICROMASTER inverters are designed to minimize conducted and radiated 
interference.  However, they are power electronic products and generate significant 
levels of interference over a wide electromagnetic spectrum. 
In many applications it is possible to operate without filters or with the built in filter.  
However, in order to achieve higher levels of attenuation an external filter may be 
required.  In particular, an external filter will be needed in order to meet residential, 
commercial and light industrial levels. 
The purpose of EMC filters is to reduce the conducted levels of interference from 
the inverter to the supply.  It is not intended to reduce radiated interference or 
attenuate interference into the inverter.  It should be fitted to the input supply to the 
inverter and will be damaged if installed in the inverter output. 
The filters are designed to mount underneath the MICROMASTER to minimize 
space requirements.  Full installation instructions and information concerning the 
appropriate filters are given in the Reference Manual. 
9.5 PROFIBUS 
Module 
Siemens Standard Drives incorporate an RS485 serial interface as standard. In 
order to operate on a PROFIBUS system a separate conversion module is 
required.  The PROFIBUS module and the PROFIBUS system is described in 
section 8.4.2. 
9.6 
Input and Output Chokes 
Chokes can be fitted to the input of the inverter to reduce harmonic distortion and 
to reduce the effect of supply disturbance on the inverter.  Chokes are also 
recommended where supply impedance is less than 1%. 
Chokes are fitted to the output of the inverter to allow operation with long cables.  
The choke compensates for the stray capacitance of the cables.  Recommended 
chokes for different cable lengths and inverters are available.