Integrated Flow Control 
68
312779E
Fluid and Air Pressure 
Requirements
The fluid input pressure to the fluid regulator must be 
high enough to provide a 15-20 psi (0.1-0.14 MPa, 
1.0-1.4 bar) pressure differential across the regulator at 
the highest flow setting. 
For example, if the maximum 
flow rate set point is 280 cc/min and 35 psi outlet pres-
sure is required to achieve that flow, the input pressure 
must be 50-55 psi.
Required air pressure to the flow control module is 
70-100 psi (0.35-0.7 MPa, 3.5-7.0 bar).
NOTE: 
For flow control modules 249849 and 24H989 used 
with a 1:1 fluid regulator, the fluid outlet pressure 
from the regulator must be between 12-75 psi 
(.08-0.5 MPa, 0.84-5.2 bar) for all flow set points. 
Flow rate set points with pressures outside this 
range are not achievable. There must be at least 12 
psi (.08 MPa, 0.84 bar) fluid pressure at the lowest 
flow rate.
If flow control module 24H989 is used with a fluid 
regulator at a ratio greater than 1:1, the relationship 
of air pressure to fluid outlet pressure is very impor-
tant. The lowest recommended air pressure from 
the V/P is 10-12 psi (.07-.08 MPa, 0.70-0.84 bar). 
Back pressure will be required to ensure minimal 
fluid pressure at the lowest flow rate setpoint.
The turn down ratio of the typical fluid regulator is 
approximately 3:1 or 4:1, depending on material type 
and viscosity. 
For example, if the lowest flow rate 
required is 100 cc/min, the top flow rate achievable may 
be 300-400 cc/min. 
NOTE: The top flow rate is not the maximum flow rate 
range selected.
Flow Control Operation
See F
. 73 for module 249849 and F
. 74 for module 
24H989. The Flow Control System includes two infor-
mation loops:
The pressure loop monitors fluid pressure with the 
pressure sensor in the module. This allows the sys-
tem to react very quickly to set point changes. The 
gun must be triggered during the pressure loop.
The flow loop monitors fluid flow through flow 
meter pulses, ensuring accuracy. The gun must be 
triggered during the flow loop.
The Flow Control System creates a data table that tar-
gets a desired flow rate based on the fluid pressure. It 
then monitors the flow loop to maintain the flow rate.