System Operation
312779E
83
General Operating Cycle, 
Sequential Dosing
1.
The system enters and loads the desired color. 
2.
The system enters Mix mode to begin operation.
3.
The ProMix 2KS controller sends signals to activate 
the solenoid valves. The solenoid valves activate 
Dose Valves A and B. Fluid flow begins when the 
Gun Trigger input is seen.
4.
Components A and B are introduced into the fluid 
integrator (FI) one at a time as follows. 
a.
Dose Valve A (DVA) opens, and fluid flows into 
the integrator. 
b.
Flow Meter A (MA) monitors the fluid volume 
dispensed and sends electrical pulses to the 
ProMix 2KS controller. The controller monitors 
these pulses and signals. 
c.
When the target volume dispenses, Dose Valve 
A closes.
NOTE: The dispense volume of component A and B 
is based on the mix ratio and dose size set by the 
user and calculated by the ProMix 2KS controller.
d.
Dose Valve B (DVB) opens, and fluid flows into 
the integrator and is aligned proportionately with 
component A. 
e.
Flow Meter B (MB) monitors the fluid volume 
dispensed and sends electrical pulses to the 
ProMix 2KS controller.
f.
When the target volume is dispensed, Dose 
Valve B closes.
5.
The components are pre-mixed in the integrator, 
then uniformly blended in the static mixer (SM). 
NOTE: To control output from the static mixer to the 
gun, install an optional fluid pressure regulator.
6.
Components A and B are alternately fed into the 
integrator as long as the Gun Trigger input is seen. 
7.
If the Gun Trigger input is not seen for two minutes, 
the system switches to Idle mode, which closes off 
the mix manifold dose valves. 
8.
When the Gun Trigger input is seen again, the Pro-
Mix 2KS continues the process where it left off.
NOTE: Operation can be stopped at any time by 
going to Standby mode (remove Mix input).
Table 11: Sequential Dosing Operation
Ratio = 2.0:1
Dose 1
Dose 2
Dose 3
A = 2
B = 1