a. Select 5 CM xfer fnct. Enter the transmitter transfer function for the 
meter. Select sq root to display flow units. The custom meter transfer 
function is independent of the analog output transfer function.
8. Select 
SEND (F2) 
to upload the configuration to the transmitter.
FIGURE 6-1. Exploded View of 
the Rosemount 3051N with 
Optional LCD Meter.
Installing the Meter
For transmitters ordered with the LCD meter, the meter is shipped installed. 
Installing the meter on an existing Rosemount 3051N transmitter requires a 
small instrument screwdriver and the meter kit (when the kit is made available 
by Rosemount Nuclear Instruments, Inc.).
To maintain the Rosemount 3051N qualification status, any piece parts for the 
Rosemount 3051N (if available) must be supplied by RNII.
The meter kit includes:
one LCD meter assembly
one extended cover with O-ring installed
two nylon standoffs
two captive screws
one ten-pin interconnection header
1.
IF the transmitter is installed in a loop, THEN secure the loop and 
disconnect power.
2. Remove the transmitter cover opposite the field terminal side. Do not 
remove the instrument covers in explosive environments when the circuit 
is alive.
3. Remove the failure mode and alarm jumpers from the electronics module 
and insert them in their new positions above and below the meter 
readout on the meter assembly.
Interconnecting Pins
Jumpers (Top and Bottom)
LCD Meter
Extended 
Cover
See “Safety Messages” in Section 6 for warning information.