Note
Wintertime Operation:
The Marley fill system used in the AV Series cooling tower has air entrance 
louvers that are molded integrally as part of the fill. This feature makes 
these towers very forgiving of cold weather operation, even at the low 
temperature  and  reduced  load  conditions  encountered  in  free  cooling 
and other low temperature applications. Nevertheless, during operation 
in subfreezing weather the opportunity exists for ice to form in the colder 
regions of the tower. 
Slushy, transitory ice forms routinely in the colder regions of the fill
of low temperature towers, and is visible through the tower louvers. 
Such  ice  normally  has  no  adverse  effect  on  tower  operation,  but 
its appearance should be a signal to the operator to undertake ice
control procedures.
It is the operator's responsibility to prevent the formation of destruc-
tive (hard) ice on the cooling tower fill. Certain guidelines should be
followed:
 1.  Do not allow the tower’s leaving water temperature to drop below a 
minimum allowable level—say 36°F to 40°F (2°C to 4.5°C). If such 
low temperature operation is necessary or beneficial to your process, 
establish the minimum allowable level as follows:
    During the coldest days of the first winter of operation, observe whether 
any ice is forming on the louver face, particularly near the bottom 
part of the louver face. If hard ice is present on the louvers, you must 
increase the allowable cold water temperature. If the coldest possible 
water is beneficial to your process, ice of a mushy consistency can 
be tolerated—but routine periodic observation is advisable.
If the minimum allowable cold water temperature is established at 
or near minimum heat load, it should be safe for all operating condi-
tions. 
Having established the minimum allowable cold water temperature, main-
taining that temperature can be accomplished by fan manipulation, as 
outlined in 
item 4 under Tower Operation. However, in towers of more 
than  one  cell,  where  fans  are  manipulated  sequentially,  please  realize 
that the water temperature will be significantly lower in the cell or cells 
operating at the highest fan speed than the net cold water temperature 
 
Caution
Operation