HDV Series Direct Vent Gas Fireplace
CHeCK GAS PReSSuRe and eleCtRICAl INStAllAtIoN - MIllIVolt
1.  Check gas type. The gas supply must be the same as stated 
on the appliance’s rating decal. If the gas supply is differ-
ent from the fireplace, StoP! Do not install the appliance. 
Contact your dealer immediately.
.  To ease installation, a 18" (457 mm) flex line with manual 
shut-off  valve  has  been  provided  with  on  this  appliance. 
Install and attach 1/" gas line onto shut-off valve. 
3.  After completing gas line connection, purge air from gas line 
and test all gas joints from the gas meter to the fireplace for 
leaks. Use a solution of 50/40 water and soap or a 
gas sniffer. 
4.  To adjust flame height, turn HI/LO knob to HI to get 
maximum pressure to burner. Turn HI/LO knob to 
LO to get minimum pressure. 
5.  To  check  gas  pressures  at  valve,  turn  captured 
screw counter clockwise  or 3 turns and then place 
tubing to pressure gauge over test point. Turn unit 
to high. Figure 43. After taking pressure reading, 
be sure and turn captured screw clockwise firmly 
to  reseal.  Do  not  over  torque.  Check  test  points  for  gas 
leaks.
Note:  Captured screws for pressure reading are located in 
the same place in all three valve types: Millivolt, Electronic and 
Remote Hi/Lo.
FP1979
Millivolt gas valve
FP1979
Figure 43 - 
Gas Pressure Check at Gas Valve 
Pressure 
Test “IN”
Pressure 
Test “OUT”
HI/LO Knob
Pilot Adjustment Screw 
W
ARNING
Do  not  use  open  flame  to  check  for  gas 
leaks.
eleCtRICAl WIRING
This fireplace will work without any electrical supply except to operate blowers, electronic igni-
tion system and Hi/Lo remote control receiver.
Note: If installed in mobile home, fireplace must be bolted securely to floor. 
W
ARNING
electrical connections should only be performed 
by a qualified, licensed electrician. Main power 
must be off when connecting to main electrical 
power supply or performing service. All wiring 
shall be in compliance with all local, city and 
state codes. the appliance, when installed, must 
be  electrically  grounded  in  accordance  with 
local codes or in the absence of local codes, 
with the National electrical Code ANSI/NFPA 70 
(latest  edition)  and  Canadian  electrical  Code, 
CSA C22.1.
CA
ut
Io
N
label all wires before disconnecting when 
servicing controls. Wiring errors can cause 
improper and dangerous operation.
Verify proper operation after servicing.