Monessen Hearth CL)NVC/PVC Manuel D’Utilisation

Page de 52
42D0200
Designer Series Gas Fireplaces
27
1.  Check gas type. The gas supply must be the same as 
stated on the appliance’s rating decal. If the gas supply 
is different from the fireplace, SToP! Do not install the 
appliance. Contact your dealer immediately.
2.  To ease installation, a 30" (762 mm) flex line with manual 
shut-off valve has been provided with on this appliance. 
Install and attach 1/2" gas line onto shut-off valve. 
3.  After completing gas line connection, purge air from 
gas line and test all gas joints from the gas meter to 
the fireplace for leaks. Use a solution of 50/50 water 
and soap or a gas sniffer. 
4.  To adjust flame height, turn HI/LO knob to HI to get 
maximum pressure to burner. Turn HI/LO knob to 
LO to get minimum pressure. 
5.  To check gas pressures at valve, turn captured screw 
counter clockwise 2 or 3 turns and then place tubing 
to pressure gauge over test point. Turn unit to high.  
Figure 37. After taking pressure reading, be sure and 
turn captured screw clockwise firmly to reseal. Do 
not over torque. Check test points for gas leaks.
ELECTRICaL wIRING
This fireplace will work without any electrical supply. Electricity is only needed to operate blower.
NoTE: If installed in mobile home, fireplace must be bolted securely to floor. 
FP1979
Millivolt gas valve
Figure 37 - 
Gas Pressure Check at Gas Valve 
Pressure 
Test “IN”
Pressure 
Test “OUT”
HI/LO 
Knob
Pilot Adjustment Screw 
FP1979
w
a
RNING
do  not  use  open  flame  to  check  for  gas 
leaks.
w
a
RNING
Electrical connections should only be performed 
by a qualified, licensed electrician. Main power 
must be off when connecting to main electrical 
power supply or performing service. all wiring 
shall be in compliance with all local, city and 
state codes. The appliance, when installed, must 
be  electrically  grounded  in  accordance  with 
local codes or in the absence of local codes, 
with the National Electrical Code aNSI/NFPa 70 
(latest  edition)  and  Canadian  Electrical  Code, 
CSa C22.1.
C
au
TI
o
N
Label all wires before disconnecting when 
servicing controls. wiring errors can cause 
improper and dangerous operation.
Verify proper operation after servicing.
MILLIvoLT & ELECTRoNIC ChECK GaS PRESSuRE and ELECTRICaL INSTaLLaTIoN