vENTING INSTaLLaTIoN 
BELow GRadE INSTaLLaTIoNS
When it is not possible to meet the required vent terminal clearances of 12" above grade level, 
a snorkel kit is recommended. It allows installation depth down to 7" (178 mm) below grade 
level. The 7" (178 mm) is measured from the center of the horizontal vent pipe as it penetrates 
through the wall.
Ensure  that  sidewall  venting  clearances  are  observed.  If  venting  system  is  installed 
below ground, we recommend a window well with adequate and proper drainage to be 
installed around the termination area.
If installing a snorkel, a minimum 24" vertical rise is necessary. The maximum horizontal run 
with the 24” vertical pipe is 36". This measurement is taken from the collar of the fireplace (or 
transition elbow) to the face of the exterior wall. Refer to the Sidewall Venting Graph for extended 
horizontal run if the vertical exceeds 24".
1.  Establish vent hole through the wall. Refer to Page 18, Figure 17 
2.  Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe. Install 
window well (not supplied). Refill hole with 12" of coarse gravel leaving a clearance of approxi-
mately 4" below snorkel. Figure 28
3.  Install vent system.
4.  Ensure  a  watertight  seal  is  made  around  the  vent  pipe 
coming through the wall.
5.  Slide  the  snorkel  into  the  vent  pipes  and  secure  to  the 
wall.
6.  Level the soil so as to maintain a 4" clearance below snor-
kel. Figure 28
If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of 
the snorkel. Fasten brackets to wall first, then secure to snorkel with self drilling #8 x 1/2" sheet 
metal screws. It will be necessary to extend vent pipes out as far as the protruding wall face. 
Figure 28
w
a
RNING
•  do not back fill around snorkel.
•   a  clearance  of  at  least  4”  must  be 
maintained between the snorkel and the 
soil.
FP1965
below grade install
Figure 28 -  
Below Grade Installation
Screws
Minimum 
4" Clearance
Ground
Window Well 
Gravel 
Drain 
Foundation Wall 
Firestop 
24"
Minimum 
FP1965
FP1966
snorkel
Figure 29 - 
Snorkel Installation, Recessed Foundation
Foundation
Recess 
Watertight Seal 
Around Pipe 
Sheet Metal 
Screws 
Wall Screws 
Snorkel 
FP1966