5. PROTECTION FUNCTION 
5.1 Symbol & Meaning 
TA: Indoor ambient temperature;   
TE: Indoor evaporator temperature; 
TS: Setting temperature through the remote controller. 
 
5.2 Protection Function 
 
  3 minute compressor time delay 
The compressor will wait for 3 minutes before restarting, so as to prevent the pressure 
imbalance in refrigerant system from resulting in compressor rotor locking. 
 
 
  Anti-freezing protection in cooling or dry mode 
Anti-freezing function is activated according to TE. 
If TE is lower than 33.8°F (1
℃) for 14 minutes, the evaporator anti-freezing protection will be 
activated. The compressor will turn off for 5 minutes. 5 minutes later, if the evaporator pipe 
temperature is still lower than 33.8°F (1
℃), the compressor remain off; when it gets higher 
than 33.8°F (1
℃), the compressor will restart and the antifreeze function will be cancelled.   
Note:
 If the compressor stops operation, the time will be cleared. 
If the fan motor turns to High speed or the indoor ambient temperature gets over 78.8°F 
(26
℃), the time will keep inactive, not be cleared. 
 
 
  Anti-frosting protection and defect at cooling or dry mode 
After compressor runs for 3 minutes, if TE is less than 5°F (-15℃) for the subsequent 3 
minutes, the anti-frosting protection will be activated and the compressor will stop for the 
following 6 minutes. After that time, if the condition for de-frosting function is met again in the 
following 10 minutes while the compressor is operating, the unit will display ‘
Ed’ to indicate that 
the unit is in the defrost mode defect. The compressor and fan motor will turn OFF 
  Note: The Defect display can be cancelled only by pressing the ON/OFF button on the unit 
or the remote controller. 
 
 
 
 